Table 5: R Series troubleshooting
Problem
Panel detail display: Annunciator 000 Communication Fault
Annunciator LCD and LEDs are inoperative
Annunciator control switches don't work
Lamp test
8
Cause
Communication wiring has an open fault
Communication wiring polarity is reversed
Annunciator has no power
Annunciator address DIP switches are set incorrectly (on the
annunciator shown in the panel message)
Annunciator network baud rate DIP switch is set incorrectly (for
normal operation use 9600 baud)
Annunciator has no power
Remote key switch is in the "locked" or disabled position
Password entry may be required (see "Entering a password"on
page 16)
During a lamp test the annunciators with LCDs show the
version of annunciator firmware currently loaded