Routing cables; connecting and installing bus connectors
Correct shield
installation
5-10
Observe the following points:
Use cable clamps made of metal to secure the braided shield.
The enclosing clamps must hold a large part of the shield and make good
contact (see Fig. 5-1).
Connect the shield to a shield busbar immediately adjacent to the point
where the cable enters the cabinet.
Figure 5-1

Securing shielded cables with cable clamps and cable ties

ET 200 Distributed I/O System
EWA 4NEB 780 6000-02a