Clearances - Quadra-Fire DV400S Owner's Manual And Installation Instructions

Direct vent room heater
Table of Contents

Advertisement

DURA-VENT GS
CATALOG #
953
963
988
981
982
971
980
984
909B
950
3951
3960
HHW2
HHW2K
The following clearances to combustibles must be main-
tained:
Minimum clearances to the floor - 0"
Back of unit to wall - 6"
Sides of unit to wall - 6
Base of the unit to ceiling - 72".
Minimum clearances to Venting are as follows:
Horizontal runs require a 1-1/2" minimum Air Space on the top and
an 1/2" minimum Air Space on the sides and bottom of the outer
Vent Section. If an Elbow is being used,in an enclosed wall, floor
or ceiling, a top Air Space clearance of 3" must be maintained.
Vertical rise sections require a 1" minimum Air Space completely
around the Vent section. These clearances must be maintained
at all times.
This appliance is certified for installation in a bed/sitting room in
the U.S. and Canada.
Mobile Home Installations. Appliances installed in Mobile Homes
must be secured to the floor in a minimum of two locations.
Positioning the Appliance.
This appliance may be placed on a combustible or non-combus-
tible continuous, flat surface. When the appliance is installed
directly on carpeting, tile or other combustible material other than
wood flooring, the appliance shall be installed on a metal or wood
panel extending the full width and depth of the appliance. Slide
the Heater into position and level the Heater from side-to-side
and front-to-back. Shim as necessary.
March 4, 2002
R
VENTING SYSTEM COMPONENTS
Storm Collar
Firestop Spacer
Wall Strap
Snorkel Termination (36")
Snorkel Termination (14")
Horizontal Kit (Horizontal Termination Cap, One 90 Degree Black Elbow, Wall
Thimble, 24" Black Pipe, 11" - 14 5/8" Adjustable Vent
Vertical Termination Cap with Wind Halo
Horizontal Termination Cap
Retrofit Adjustable Chimney Connector Retrofit Chimney Connector Plate
VSS - Vinyl Siding Standoff/Shield
Round Ceiling Support/Wall Thimble Trim Kit, Polished Brass
Cathedral Ceiling Support Trim Kit, Polished Brass
Horizontal High Wind Cap (recommended for optimal performance)
Horizontal Kit (One 90 degree Elbow, Wall Thimble, 24" Black Pipe, 11" - 14 5/8"
Adjustable Vent, HHW2 Termination Cap.

CLEARANCES

DV400S DIRECT VENT ROOM HEATER
DESCRIPTION
Minimum Clearances To Combustibles
6"
HEARTH PROTECTION IS NOT
NECESSARY ON THIS GAS HEATER.
Page 8
Figure 1
4"
6"
6"
6"
48"
MAX.
4"
30211C