Existing Masonry Chimney Installation - Quadra-Fire DV400S Owner's Manual And Installation Instructions

Direct vent room heater
Table of Contents

Advertisement

2 Ft. Min.
LISTED
2 Ft.
CAP
Min.
LOWEST
DISCHARGE
OPENING
Roof Pitch
flat to 6/12
6/12 to 7/12
over 7/12 to 8/12
over 8/12 to 9/12
over 9/12 to 10/12
over 10/12 to 11/12
over 11/12 to 12/12
over 12/12 to 14/12
over 14/12 to 16/12
over 16/12 to 18/12
over 18/12 to 20/12
over 20/12 to 21/12
Figure 10 -Vent (Chimney) Height
WARNING
WHEN VENT SECTIONS EXCEEDING 3 FEET
IN LENGTH ARE INSTALLED BETWEEN AN
OFFSET/RETURN, STRUCTURAL SUPPORT
MUST BE PROVIDEDTO REDUCE OFF-CENTER
LOADING AND PREVENT VENT SECTIONS
FROM SEPARATING AT THE VENT JOINTS.
March 4, 2002
R
HORIZONTAL OVERHANG
VERTICAL WALL
X
12
ROOF PITCH IS X/12
H (MIN.)-MINIMUM HEIGHT
FROM ROOF TO LOWEST
DISCHARGE OPENING
H (min.) ft.
1.0
1.25
1.5
2.0
2.5
3.25
4.0
5.0
6.0
7.0
7.5
8.0
DV400S DIRECT VENT ROOM HEATER
SEAL WITH SILICONE
SEAL WITH SILICONE
24" MINIMUM
VERTICAL HEIGHT
DURA-VENT GS
VENTING
Adaptation to Masonry Chimney
C. Existing Masonry Chimney Installation
This installation is subject to local jurisdic-
tion. Some codes may require the use of
another liner for intake air. If so, the 4"
aluminum liner should be inside a 6" UL 181
listed liner.
This Heater can be vented through an existing
Masonry Chimney but the chimney must be lined
with one UL 1777 listed 4" aluminum flexible gas
vent liner for exhaust. The existing Flue will be
used to supply the air intake to the galvanized
steel Flue system. See Figure 11.
Page 16
INTAKE AIR
WALL THIMBLE/
TRIM COLLAR
6"
Figure 11
EXHAUST
4'' UL 1777 LISTED
GAS VENT INNER
FLEX LINER
INSIDE CHIMNEY
DIAMETER
6" MINIMUM
30211C