Unit Settings
DM word
Value
Number of input data areas
m+7
0000
0001
0002
other
m+8
Input area 1 : start address in the input buffer
0000 ~ 0510
other
m+9
Input area 1 : start address in the CPU
0000 ~ 4095
0000 ~ 5999
A000 ~ A235
A300 ~ A511
B000 ~ B099
C000 ~ C063
other
m+10
Input area 1 : size
0000 ~ 0100
other
m+11
see m+8
m+12
see m+9
m+13
see m+10
1
*
Setting errors are indicated in IR n+2 (see section 5-3) and the ERR LED will
be flashing to indicate a non-fatal error.
2
*
If the specified number of words would make the area exceed the boundaries of
the available buffer, DM, LR, IR or HR areas, the actual number of transferred
words will be limited as to remain within all of these boundaries. This setting
error is indicated in IR n+2 (see section 5-3) and the ERR LED will be flashing
to indicate a non-fatal error.
Notes • The Unit does not check the validity of the contents of any PLC data area,
from which output data is to be transferred. Any data present in the area
will be transferred to the output buffer of the Unit.
• If multiple fieldbus masters (e.g. PROFIBUS-DP, CompoBus/D, SYSMAC
BUS) are mounted on the same PLC system, only one of them can be
used in default mapping mode. The Unit does not check if the mapped
PLC input area is in use by other Units. If so, this Unit's data may
overwrite another Unit's data, or vice versa.
• If the settings cause two destination areas to overlap, the data of the
higher number area will overwrite the lower. This practice is to be avoided
by the user.
Meaning
Default mapping
C200HS:
Unit input buffer bytes 000 ~ 063 are mapped to
PLC addresses IR350 ~ IR381
C200HE,C200HG,C200HX:
Unit input buffer bytes 000 ~ 099 are mapped to
PLC addresses IR350 ~ IR399
One user-defined data input area
Two user-defined data input areas
Default mapping (see value 0000)
Byte 000 ~ 510 (even) in input buffer of the Unit
1
Setting error *
, input area is ignored
DM0000 ~ DM4095 (C200HE-CPU11)
DM0000 ~ DM5999 (all other CPUs)
IR000 ~ IR235
IR300 ~ IR511
HR00 ~ HR99
LR00 ~ LR63
1
Setting error *
, input area is ignored
000 ~ 100 words to be transferred from Unit input
2
buffer to PLC *
1
Setting error *
, input area is ignored
Input area 2 : start address in the input buffer
Input area 2 : start address in the CPU
Input area 2 : size
Section 5-1
55