Should you wish to achieve the required water quality by using chemical addi-
tives, then this is your own responsibility. The warranty on the product delivered by
A.O. Smith expires, if the water quality does not meet A.O. Smith's specifications or
the chemical additives have not been approved by A.O. Smith.
-
On installation and during additions or changes at a later stage, A.O. Smith recom-
mends to keep a record of the type of water used, its quality at the time, and if ap-
plicable, which additives and quantities were added.
Parameter
Water type
Softened water
pH
Conductivity (at 20°C in µS/cm)
Iron (ppm)
Installation volume/capacity 1-7
<20 l/kW
Installation volume/capacity
>=20 l/kW
Oxygen
Max. 5% filling water addition annually
Corrosion inhibitors
pH increasing or lowering agents
Anti-freeze additives
Other chemical additives
Solid substances
Residues of processing water not for-
ming part of the drinking water
Water type definition:
Potable water:
Tap water compliant with the European drinking water guideline:
98/83/EG dated 3 November 1998.
Softened water:
Water with partly de-ionised calcium and magnesium.
Demi-water:
Virtually completely demineralised water (very low conductivity)
Distilled water:
Water no longer containing minerals.
Value
Potable water
6.0-8.5
6.0-8.5
Max. 2500
Max. 0.2
Hardness (°dH)
1-12
Refer to Additives Attachment
1-7
No oxygen diffusion allowed during ope-
ration.
Refer to Additives Attachment
Refer to Additives Attachment
Refer to Additives Attachment
Refer to Additives Attachment
Refer to Additives Attachment
Not allowed
Not allowed
table 6.3.a