Switch Actuator 16A, 2 Switches; 1.2.1 Technical Data - ABB 2CSYK1102C/S Product Manual

Switch actuator with rocker switches
Table of Contents

Advertisement

MYLOS
Building Automation
®
1.2
Switch Actuator 16A, 2 switches
2CSYK1103x
Power supply
Nominal output values
Connections
Control and display elements
EIB / KNX
EIB / KNX voltage
Ambient temperature
Execution
Case, colour
CE marking
The one-channel 16A Switch Actuator two switches is a flash-mounted device for the ABB's
Mylos Building Automation system.
On the rear side, the device has an exchange output contact (NA/NC) that can be configured
for the control of different kinds of loads. These contacts need additional power supply. The
device relay can receive a switching command from the device itself, from other control
devices of the Building Automation system or from conventional control devices (push-
buttons, switches, relays) duly associated with input devices of the Home Automation
system. For the simple output it is possible to control the following functions separately:
-
Time, delay, ON/OFF functions;
-
Stairlights with pre-warning and adjustable time for stairway lighting functions;
-
Scene control through 8 bit /1 bit controls
-
AND, OR, XOR logic operation and gate function.
On the front side it has two rocker switches with programmable indicator light, that can be
configured separately according to the following functions:
-
simple switching or switching with two communication objects
-
Dimmer functionality;
-
Shutter functionality;
-
1 bit and 8 bit scene functionality;
-
manual operation that makes it possible to control the relays directly.

1.2.1 Technical data

- Operating voltage
- Absorbed power EIB / KNX
- Number of voltage-free contacts 1
- Rated voltage U
- Rated current I
- Mechanical contacts duration
- Number of relay changes of
position to the minimum
- EIB / KNX
- Load circuit
- Connection cable cross section
- Tightening torque
- red LED and EIB / KNX button
- SELV 24 VDC (safety extra low
voltage)
- Use
- Storage
- Transport
- Dimensions (H x W x D) in mm
- Width W in mm
- Mounting width in mm
- Mounting depth in mm
- Plastic container, white or black
- acc. to EMC and Low-Voltage
Directives
Technical features
n
(per output)
n
21...30 VDC over the bus
< 12 mA
240/400 VAC (50/60Hz)
16A
>5*10
6
40
Connection terminal
Bus 0.6-0.8 mm ø, unipole
Screw terminals
0,2....2,5 mm
braid
2
0,2....4 mm
unipole
2
Max. 0.5 Nm
To set the physical address
-5 °C ... + 45 °C
-25 °C ... + 55 °C
-25 °C ... + 70 °C
17 x W x 15
17
7
5
MYLOS
Building Automation | Technical features 5
®

Advertisement