6.3.5
Motor temperature detection signal
When motor temperature exceeds the detection level, motor temperature detection signal (Y55) is output.
(Set Pr. 407 Motor temperature detection filter ≠ "9999")
Set "55 (positive logic)" or "155 (negative logic)" in the following parameters to output the motor
temperature detection signal (Y55) when motor temperature exceeds the detection level.
⋅ Pr.190 to Pr.196 Output terminal function selection (Refer to the Instruction Manual of the inverter for details.)
⋅ Pr.313 to Pr.319 DO0 to DO6 output function selections (Refer to the Instruction Manual of FR-A7AY for details.)
⋅ Pr.320 to Pr.322 RA1 to RA3 output function selections (Refer to the Instruction Manual of FR-A7AR for details.)
Use the following parameter to adjust the temperature to output the motor temperature detection signal
(Y55).
Parameter Number
750 *
Motor temperature detection level
* Read/write is enabled when using FR-A7AZ.
REMARKS
⋅ The motor temperature detection signal is not available when Pr. 407 = "9999".
Name
Pr. 750
OFF
Y55
Y55 signal turns OFF when motor temperature
become Pr. 750 or less (with hysteresis).
MOTOR THERMISTOR INTERFACE
Minimum setting
Initial Value
increments
75°C
Hysteresis range (5 C)
Motor temperature
Time
ON
OFF
Setting Range
1°C
0 to 200°C
6