6.3.5
Motor temperature detection signal
When motor temperature exceeds the detection level, motor temperature detection signal (Y55) is output. (Set Pr.407 Motor
temperature detection filter "9999")
Set "55 (positive logic)" or "155 (negative logic)" in the following parameters to output the motor temperature detection signal
(Y55) when motor temperature exceeds the detection level.
• Pr.190 to Pr.196 Output terminal function selection (Refer to the Instruction Manual (Detailed) of the inverter for details.)
• Pr.313 to Pr.319 DO0 to DO6 output function selections (Refer to the Instruction Manual of FR-A8AY for details.)
• Pr.320 to Pr.322 RA1 to RA3 output function selections (Refer to the Instruction Manual of FR-A8AR for details.)
Pr.
Pr. group
*1
M061
750
*1
Setting can be made only when the FR-A8AZ is mounted.
NOTE
• The motor temperature detection signal is not available when Pr.407 = "9999".
44
MOTOR THERMISTOR INTERFACE
Name
Motor temperature detection level
Pr.750
OFF
Y55
Setting range
0 to 200
Hysteresis range (5°C)
Motor temperature
Time
ON
OFF
Y55 signal turns OFF when motor temperature
become Pr.750 or less (with hysteresis).
Minimum
setting
Initial value
increments
1