SECTION K CONDENSATE DRAIN
WARNING:
All condensation should be disposed of according to local, county, state, and federal laws. Refer to
NFGC, section 7.9, for additional information.
The Condensing Heat Exchanger (CHX) can generate up to 1 (one) gallon per hour (GPH) of condensate for every 100,000
BTUH. The maximum condensation rate for the ADB 751 is 7.5 GPH, the ADB 1001 is 10 GPH, and the ADB1501 is
15 GPH.
Figure K-1
CONDENSATE TRAP ALIGNMENT