Service; Repair Section - Raypak RAYTHERM 133-4001 Installation & Operating Instructions Manual

Raytherm heating boilers type h
Hide thumbs Also See for RAYTHERM 133-4001:
Table of Contents

Advertisement

Extension Pieces (5)
P/N 052871F - 5/8 DIA.

Service

Repair Section

Tube Cleaning Procedure
Establish a regular inspection schedule, the frequency
depending on the local water condition and severity of
service. Do not let the tubes clog up solidly. Clean out
deposits over 1/16" in thickness.
The boiler may be cleaned from the side opposite the
water connections as shown, without breaking pipe
connections. It is preferable, however, to remove both
headers for better visibility through the tubes and to be
sure the residue does not get into the system.
Note that you do not remove the top pan or the heat
exchanger generally. After reaming with the auger,
mount the wire brush and clean out the debris remain-
ing in the tubes. Another method is to remove the heat
exchanger, ream tubes and immerse heat exchanger
in noninhibited de-scale solvent.
RAYPAK TUBE CLEANING KIT
Auger with Carbide Tip
Fig. 51: Raypak Tube Cleaning Kit
Burner Tray Removal
1. Shut-off power and gas supply to the boiler.
2. Disconnect wires at gas valve and slide burner
Gas Valve Removal
1. Shut-off gas supply to the boiler. Remove gas pip-
2. Disconnect wires, pilot tubing and bleed line, if
3. Turn vertical gas pipe from manifold slightly and
4. Reverse above procedure to re-install.
Main Burner And Orifice Removal
1. Remove screws and burner hold-down bracket.
COMBINATION FLAME SENSOR/
IGNITER AND PILOT BURNER
Fig. 52: Typical Burner Tray Illustrated
38
P/N 052870F - 7/8 DIA.
Disconnect union(s) and pilot tubing, then loosen
and remove burner hold-down screws.
tray out.
ing to gas valve inlet.
required.
unscrew gas valve.
Wire Brush

Hide quick links: