4-3. STANDARD OPERATION DATA (REFERENCE DATA)
Operation
Indoor
Ambient
temperature
Outdoor
No. of connected units
Indoor unit
No. of units in operation
Model
Operating
conditions
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Outdoor unit
Voltage
Compressor frequency
LEV opening Indoor unit
Pressure
High pressure/Low pressure
Discharge
Heat exchanger outlet
Outdoor
unit
Accumulator inlet
Temp. of
each section
Compressor inlet
LEV inlet
Indoor unit
Heat exchanger inlet
OCH668B
PUMY-SP112VKM.TH(-BS)
PUMY-SP112VKMR1.TH(-BS)
PUMY-SP112YKM.TH(-BS)
PUMY-SP112YKMR1.TH(-BS)
27/19°C
20°C
DB/
WB
35°C
7/6°C
4
Unit
4
25
2 + 32
2
×
×
5
m
2.5
15
Hi
kg
6.5
A
15.69
14.88
V
230
230
Hz
57
74
Pulse
226
396
MPaG
2.96/1.08
1.93/0.63
67.6
43.1
48.5
2.0
14.8
-1.2
°C
15.7
-1.6
30.6
25.2
16.6
39.2
16
PUMY-SP125VKM.TH(-BS)
PUMY-SP125VKMR1.TH(-BS)
PUMY-SP125YKM.TH(-BS)
PUMY-SP125YKMR1.TH(-BS)
27/19°C
20°C
35°C
7/6°C
4
4
25
1 + 32
3
×
×
5
2.5
15
Hi
6.5
18.78
18.38
230
230
65
84
264
335
3.12/1.02
2.06/0.60
3.25/0.99
81.6
46.4
49.9
1.3
17.6
-2.0
19.6
-2.7
32.7
44.6
14.5
24.4
PUMY-SP140VKM.TH(-BS)
PUMY-SP140VKMR1.TH(-BS)
PUMY-SP140YKM.TH(-BS)
PUMY-SP140YKMR1.TH(-BS)
27/19°C
20°C
35°C
7/6°C
4
4
32
2 + 40
2
×
×
5
2.5
15
Hi
6.5
22.27
19.62
230
230
73
88
262
358
2.08/0.60
83.9
47.6
51.2
-0.3
15.4
-2.4
17.5
-2.8
33.7
45.0
14.3
26.5