Maintenance; Normal Maintenance; Electric Heat Minimum Supply Air; Indoor Blower Specifications - York LATITUDE JP024-060 Installation Manual

R-22, 13 seer
Table of Contents

Advertisement

Table 9: Electric Heat Minimum Supply Air
Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
060
(5.0)
Table 10: Indoor Blower Specifications
Size
(Tons)
HP
RPM
024
1/2
1100
(2.0)
030
1/2
1100
(2.5)
036
1/2
1100
(3.0)
042
1
1100
(3.5)
048
1
1100
(4.0)
060
1
1100
(5.0)
Table 11: Electric Heat Multipliers
Voltage
Nominal
240
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.

Maintenance

Normal Maintenance

Prior to any of the following maintenance procedures,
shut off all power to the unit, to avoid personal injury.
Periodic maintenance consists of changing or cleaning filters
and general cleaning of the outdoor coil.
FILTERS - Inspect once a month. Replace Disposable or clean
Permanent Type as necessary. DO NOT replace Permanent
Type with Disposable.
Johnson Controls Unitary Products
Voltage
5.0
208/230-1-60
800
208/230-1-60
800
208/230-1-60
800
208/230-1-60
1300
208/230-1-60
1300
208/230-1-60
1300
Motor
Eff.
SF
Frame
0.8
1.0
48
0.8
1.0
48
0.8
1.0
48
0.8
1.0
48
0.8
1.0
48
0.8
1.0
48
Applied
208
230
Minimum Supply Air (CFM)
Heater kW
6.5
10.0
15.0
800
800
750
800
800
750
800
800
750
1300
1270
1270
1300
1270
1270
1300
1270
1270
kW Capacity Multipliers
0.75
0.92
MOTORS - Indoor and outdoor fan motors are permanently
lubricated and require no maintenance.
OUTDOOR COIL - Dirt should not be allowed to accumulate on
the outdoor coil surface or other parts in the air circuit. Cleaning
should be as often as necessary to keep the coil clean. Use a
brush, vacuum cleaner attachment, or other suitable means. If
water is used to clean the coil, be sure that the power to the unit
is shut off prior to cleaning.
Exercise care when cleaning the coil so that the coil fins
are not damaged.
Do not permit the hot condenser air discharge to be
obstructed by overhanging structures or shrubs.
1
161036-YIM-E-1008