Technical Specifications

Sensor resistance table
Tem-
Resist-
perature
ance
[ºF / ºC]
[Ω]
5 / –15
36475
14 / –10
27665
23 / –5
21166
32 / 0
16325
41 / 5
12695
50 / 10
9995
Technical data
Dimensions:
Weight:
Power supply:
Max. ambient temperature
H Storage and transport:
H Operation:
Relay outputs
Breaking capacity
H Pump relay:
H Relay fault message:
Terminal connection:
Sensor inputs
Outdoor temperature sensor/
Supply temperature sensor:
Terminal connection:
Switch inputs
External heat demand,
party (override) switch:
Terminal connection:
48
Tem-
Resist-
perature
ance
[ºF / ºC]
[Ω]
59 / 15
7885
68 / 20
6245
77 / 25
5000
86 / 30
4028
95 / 35
3265
104 / 40
2663
8.3 × 6.4 × 2.1 inches
210 × 162 × 53 mm
1.5 lb / 700 g
12 V, 60 Hz, 6 VA
–4 to+140 ºF
–20 to +60 ºC
–4 to+104 ºF
–20 to +40 ºC
max. 230 VAC/4(2) A
max. 230 VAC/1(0.5) A
max. 224 V–/~2 A
0.5 to 2.5 mm
NTC sensors
0.5 to 1.5 mm
potential-free switching contacts
0.5 to 2.5 mm
Tem-
Resist-
perature
ance
[ºF / ºC]
[Ω]
113 / 45
2185
122 / 50
1801
131 / 55
1493
140 / 60
1244
149 / 65
1041
158 / 70
876
2
2
2
Tem-
Resist-
perature
ance
[ºF / ºC]
[Ω]
167 / 75
739
176 / 80
627
185 / 85
535
194 / 90
457
203 / 95
393
212 / 100
339