Technical Specifications; Sensor Resistance Chart; Technical Data - Viessmann Vitocontrol-S, WB2 Installation, Start-Up And Service Instructions Manual

For use with up to four vitodens 200, wb2-44 or wb2-60 wall-mounted condensing boilers.
Table of Contents

Advertisement

Technical Specifications

Sensor resistance chart

Temp-
Resis-
erature
tance
[ºF / ºC]
[Ω]
5 / –15
36475
14 / –10
27665
23 / –5
21166
32 / 0
16325
41 / 5
12695
50 / 10
9995

Technical data

Dimensions:
Weight
Panel weight:
Shipping weight:
Power supply:
Max. ambient temperature
H Storage and transport:
H Operation:
Relay outputs
Breaking capacity
H Pump relay:
H Relay fault message:
Terminal connection:
Sensor inputs
Outdoor temperature sensor/
supply temperature sensor:
Terminal connection:
Switch inputs
External heat demand,
"Party " (override) switch:
Terminal connection:
Temp-
Resis-
erature
tance
[ºF / ºC]
[Ω]
59 / 15
7885
68 / 20
6245
77 / 25
5000
86 / 30
4028
95 / 35
3265
104 / 40
2663
10½ × 11 × 2½ inches
265 × 280 × 60 mm
6.25 lbs / 2.8 kg
7.2 lbs / 3.3 kg
120 VAC, 7 A, 60 Hz, 1 PH
–4 to+140 ºF
–20 to +60 ºC
–4 to+104 ºF
–20 to +40 ºC
120 VAC, 6.3 A max.
120 VAC, 5 A max.
16-10 AWG
NTC sensors
16-10 AWG
potential-free switching contacts
16-10 AWG
Temp-
Resis-
erature
tance
[ºF / ºC]
[Ω]
113 / 45
2185
122 / 50
1801
131 / 55
1493
140 / 60
1244
149 / 65
1041
158 / 70
876
Temp-
Resis-
erature
tance
[ºF / ºC]
[Ω]
167 / 75
739
176 / 80
627
185 / 85
535
194 / 90
457
203 / 95
393
212 / 100
339
13