LEDs Qn
Valid for IO-Link port in SIO mode.
Table 5- 4
Q1, Q2, Q3, and Q4 LEDs
5.2
Diagnostics alarms
For each diagnostic event, a diagnostics alarm is issued and the DIAG LED flashes red on
the communication module. You can read out the diagnostics alarms, for example, in the
diagnostics buffer of the CPU. You can evaluate the error codes with the user program.
Table 5- 5
Error types
Diagnostics
Error
alarm
code
Short-circuit
1
H
Undervoltage
2
H
Overvoltage
3
H
Overtemperature 5
H
Wire break
6
H
Overflow
7
H
Underflow
8
H
Error
9
H
Communication module CM 4xIO-Link 4xM12(6ES7147-5JD00-0BA0)
Manual, 10/2017, A5E32352322-AE
Status displays of the Q1, Q2, Q3, and Q4 LEDs
Meaning
Process signal = 0 in SIO mode, deactivated or in IO-Link mode
Off
Process signal = 1 in SIO mode
On
Meaning (IO-Link error code)
Short-circuit at the process cables on the IO-Link device (1804
•
Short-circuit on IO device (7710
•
Supply voltage too low (5111
•
Supply voltage too high (5110
•
Temperature exceeded on master (1805
•
Temperature exceeded on device (4000
•
No IO-Link device connected
•
There is a break on the signal line to the IO-Link device
•
IO-Link device cannot communicate due to a different error
•
(1800
)
H
Process tag range exceeded (8C10
•
Measuring range exceeded (8C20
•
Process tag range too low (8C30
•
All IO-Link error codes which are not listed here are mapped to
•
this PROFIBUS DP error
)
H
, 5112
)
H
H
)
H
)
H
, 4210
)
H
H
)
H
)
H
)
H
Diagnostics alarms
5.2 Diagnostics alarms
IO-Link
IO-Link
master
device
X
)
H
X
X
X
X
X
X
X
X
X
27