Lochinvar ECOKNIGHT EKW46CE Installation Manual page 17

Floor standing gas fired condensing circulating type water heater
Table of Contents

Advertisement

10.4.1
FLUE TERMINAL POSITIONS
Location
Description
A
Directly below an opening, air brick, opening windows etc.
B
Above an opening, air brick, opening windows etc.
C
Horizontally to an opening, air brick, opening windows etc.
D
Below a gutter or sanitary pipework
E
Below the eaves
F
Below a balcony or car port roof
G
From a vertical drain or soil pipe
H
From an internal or external corner
I
Above ground, roof or balcony level
J
From a surface facing the terminal
K
From a terminal facing the terminal
From an opening in the car port (e.g. door, window) into the
L
dwelling
M
Vertically from a terminal on the same wall
N
Horizontally from a terminal on the same wall
P
From a vertical structure on the roof
Q
Above intersection with the roof
10.4.2
FLUE TERMINAL MINIMUM DISTANCES
Detailed recommendations for the flue system are given in BS5440-1 for equipment of rated input not exceeding 70kW net, BS6644
for equipment above 70kW net and IGE/UP/10 for equipment of rated input above 54kW net. The following notes are intended to
give general guidance only.
EKW46CE – EKW61CE
300
300
300
75
200
200
150
300
300
600
1200
1200
1500
300
300
300
EKW86CE
2000
1000
1000
75
200
200
150
300
300
1000
2000
1200
1500
600
300
300
17