Connecting-up
3.3

Instructions for EMC-correct installation

EMC (Electrom agnetic C ompatibility) involves the noise emission and noise immunity of electrical equipment.
Optional radio interference suppression filters are available to limit the noise emission.
Radio interference
suppression filter
L1'
L1
L2
L2'
Supply
L3'
L3
PE
PE'
Fig. 3.3
Location of the components
The radio interference suppression filter and drive converter must be
connected through a large surface area. The most favorable method is to
mount all of the components on a bare metal mounting panel (e.g.
galvanized steel). A line reactor must be connected between the radio
interference suppression filter and the drive converter.
The cabling should be kept as short as possible. The line feeder cable to
the radio interference suppression filter should be routed separately away
from other cables.
The motor must be connected using a screened cable, e.g. Siemens
PROTOFLEX-EMV-CY (cross-section up to 120 mm
PROTODUR NYCW (cross-section > 120 mm
connected to the motor- and drive converter housing through the largest
possible surface area to keep inductances as low as possible.
Use screened control cables to increase the noise immunity. Connect the
screens of the control cables to the mounting positions provided. Screen
clamps are provided with every SIMOVERT MASTER DRIVES to connect
the screens of the control cables (+ Fig. 3.4.1). Otherwise, cable ties can
be used to connect the screen (+ Fig. 3.4.2).
♦ Do not interrupt the screens, e.g. when installing intermediate
terminals.
♦ Control cables and power cables (= line feeder cable, motor cable)
must be routed separately away from one another.
You will find more detailed information in the brochure (Installation
instructions for EMC correct design of drives"
(Order No.: 6SE7087-6CX87-8CE0).
3-6
SIMOVERT
Line reactor
MASTER DRIVES
1U1
1U2
U1
1V1
1V2
V1
1W1
1W2
W1
PE1
Mounting panel
2
) or Siemens
2
). The screen must be
Screened
motor cable
U2
M
V2
3~
W2
PE2
Screen
clamp
Fig. 3.4.1
Fig. 3.4.2
Fig. 3.4
Siemens AG
SIMOVERT MASTER DRIVES
09.97
Cable tie
Connecting the screens of
signal cables for SIMOVERT
MASTER DRIVES
6SE7087-6BD70
Operating Instructions