Wiring Guidelines; Wiring The Controller - York YK-SMU2x0-0 Installation Instructions Manual

Yccs system manager and zone coordinator
Table of Contents

Advertisement

428546-YIM-C-1110
End-of-Line (EOL) Termination
Set to ON
System
Zone
Bus
Bus
ON
On
J8
J7
-
-
+
COM
COM
Off
S1
System Communication
Bus Terminal Strip
Figure 3: System Manager System
Communication Terminal Block Detail
Connect a Zone Communication Bus to the 3-wire
terminal block plug labeled System Bus on the ZC
(Figure 4).
End-of-Line (EOL)
Termination
Set to ON
System
Zone
Bus
Bus
ON
J8
J7
-
-
+
COM
COM
Off
S1
System
Zone Communication
Communication
Bus Terminal Strip
Bus Terminal Strip
Figure 4: Zone Coordinator System
Communication Terminal Block Detail
USB Port
The Universal Serial Bus (USB) port connects an
external memory storage device (USB memory stick,
Type U1 or U2) for backing up controller configuration
parameters or for performing upgrades.
Ethernet Port
The Ethernet connection (10 or 100 Mbps) is an 8-pin
RJ-45 network port (Figure 1). Use the Ethernet port to
connect to Internet Protocol (IP) networks for remote
user access.
Optional Internal Modem
Both the YK-SMU2-0 and the YK-ZCUx0-0 supervisory
controllers have an internal modem and a 6-pin RJ-11
modular jack. Insert a standard phone line plug to
connect the internal modem.
4
On
ON
J6
COM 24V
+
Off
S2
24 VAC Power
Not Used
Input (10 VA)
On
ON
J6
COM 24V
+
Off
S2
24 VAC Power
Input (10 VA)
YCCS System Manager and Zone Coordinator Installation Instructions

Wiring Guidelines

Follow these guidelines when wiring the System
Manager and Zone Coordinator controllers:
Securely mount the controller base before wiring.
See the Mounting the Controller section.
Route the supply power wires and communication
cables at least 50 mm (2 in.) away from the vent
slots on the sides of the controller housing.
Provide slack in the wires and cables. Keep cables
routed neatly around the controller to promote
good ventilation, Light-Emitting Diode (LED)
visibility, and ease-of-service.

Wiring the Controller

CAUTION: Risk of Property Damage.
!
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
IMPORTANT: Prevent static electricity discharge to
the controllers. Static electric discharge may
damage the controller and void any warranties.
IMPORTANT: Exceeding the controller electrical
ratings can result in permanent damage to the
controller and void any warranty.
IMPORTANT: Use copper conductors only. Make
all wiring connections in accordance with local,
national, and regional regulations. Do not exceed
the System Manager or Zone Coordinator's
electrical ratings.
To wire the controller:
1. Connect the three System Communication Bus
wires to the 3-terminal block for the System
Manager and/or connect the three Zone
Communication Bus wires for the Zone
Coordinator (Figure 3 and Figure 4).
Note: When the controllers are connected to the
System Communication Bus, you must set the
End-of-Line (EOL) switch to the ON position
(Figure 3 and Figure 4).
2. Connect the 24 VAC power supply wires from the
transformer to the terminal block (Figure 3 and
Figure 4).