Of Connect Connections Diagram Connect Ions Diagram - Honeywell Lyric LCP500-LC Installation And Reference Manual

Hide thumbs Also See for Lyric LCP500-LC:
Table of Contents

Advertisement

THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE
WITH THE NATIONAL FIRE PROTECTION ASSOCIATION
STANDARDS ANSI/NFPA 70 NATONAL ELECTRIC CODE AND
NFPA 72 NATIONAL FIRE ALARM CODE, CHAPTER 2
(NATIONAL FIRE PROTECTION ASSOC., BATTERYMARCH
PARK, QUINCY, MA 02169). PRINTED INFORMATION
DESCRIBING PROPER INSTALLATION, EVACUATION
PLANNING AND REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
POWER SUPPLY
300-04705V1
(300-04063V1 CANADA)
HARD
2K OHM
WIRED
EOLR
ZONE
HARD
2K OHM
WIRED
EOLR
ZONE
IF AN EXTERNAL CELLULAR RADIO ANTENNA IS USED, THE ANTENNA MAY BE INSTALLED OR REPLACED ONLY BY A PROFESSIONAL INSTALLER.
FOR LYRIC-3G/3GC, THE EXTERNAL ANTENNA MUST NOT EXCEED A MAXIMUM DIRECTIONAL GAIN (INCLUDING CABLE LOSS) OF 6.0 DBI AT 850 MHZ AND 2.5 DBI AT 1900 MHZ.
FOR THE LYRIC-CDMA, THE EXTERNAL ANTENNA MUST NOT EXCEED A MAXIMUM DIRECTIONAL GAIN (INCLUDING CABLE LOSS) OF 9.3 DBI AT 850 MHZ AND 8.2 DBI AT 1900 MHZ.
FOR THE LYRICLTE-A, THE EXTERNAL ANTENNA MUST NOT EXCEED A MAXIMUM DIRECTIONAL GAIN (INCLUDING CABLE LOSS) OF 3.25 DBI AT 850 MHZ, 5.5 DBI AT 1700 MHZ AND
2.5 DBI AT 1900 MHZ.
FOR THE LYRICLTE-C, THE EXTERNAL ANTENNA MUST NOT EXCEED A MAXIMUM DIRECTIONAL GAIN (INCLUDING CABLE LOSS) OF 0.6 DBI AT 850 MHZ, 5.5 DBI AT 1700 MHZ AND
2.5 DBI AT 1900 MHZ.
FOR THE LYRICLTE-V, THE EXTERNAL ANTENNA MUST NOT EXCEED A MAXIMUM DIRECTIONAL GAIN (INCLUDING CABLE LOSS) OF 7.31 DBI AT 780 MHZ AND 7.35 DBI AT 1700 MHZ.
WEEKLY TESTING IS REQUIRED TO ENSURE
PROPER OPERATION OF THIS SYSTEM
THE LYRIC CONTROLLER IS COMPATIBLE WITH THE
FOLLOWING INTEGRAL RECHARGEABLE BATTERY PACKS:
LCP500-4B (STANDARD CAPACITY)
LCP500-24B (HIGH CAPACITY)
REPLACE EVERY FOUR YEARS
LYRIC RESIDENTIAL BURGLAR AND FIRE ALARM CONTROL PANEL
No
Notes:
No
No
tes:
tes: Connection of the fire alarm signal to a fire alarm headquarters or a Central Station shall be permitted
tes:
with the approval of the local authority having jurisdiction. The burglar alarm signal shall not be connected to a
police emergency number. The System must be checked by a qualified technician once every three years
LYRIC ALSO COMPLIES WITH THE FOLLOWING:
CANADIAN STANDARDS ASSOCIATION (CSA)
C22.1, CANADIAN ELECTRICAL CODE, PART 1,
SAFETY STANDARD FOR ELECTRICAL
INSTALLATIONS AND CAN/ULC-S540
INSTALLATION OF RESIDENTIAL FIRE WARNING
SYSTEMS.
NOTE: THE HARD WIRE ZONES CANNOT BE USED AS FIRE ZONES.
TERMINAL
BOARD
TAMPER
BATTERY
RECEPTACLE
IMPORTANT NOTES ABOUT EXTERNAL ANTENNAS
SUMMARY OF CONNECTIONS
Lyric Controller Installation and Reference Guide
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE
HARMFUL INTERFERENCE, AND (2) THIS DEVICE
MUST ACCEPT ANY INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.
THIS UNIT MAY BE PROGRAMMED TO INCLUDE AN ALARM
VERIFICATION FEATURE THAT WILL RESULT IN A DELAY OF THE
SYSTEM ALARM SIGNAL FROM THE INDICATED FIRE CIRCUITS.
THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS)
SHALL NOT EXCEED 60 SECONDS. NO OTHER INITIATING
DEVICES SHALL BE CONNECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
CIRCUIT
(ZONE)
03 - 126
ZONE TYPE -
SUPERVISED
FIRE WITH
VERIFICATION
- 39 -
USB PORT
WARNING
CONTROL UNIT
SMOKE DETECTOR
DELAY-SEC
MODEL
DELAY-SEC
30 seconds
5806W3
10 seconds
lyric-SOC-V5