Return Air Provisions; Air Distribution Systems - Nordyne M2RC-080 Installation Instructions Manual

Direct vent (sealed combustion) forced air gas furnaces: m2rc series 90+ upflow and m2rl series 90+ downflow condensing furnace
Table of Contents

Advertisement

RETURN AIR PROVISIONS
Upfiow models draw the return air from the
base of the furnace. A stand or return air duct
must be supplied to the furnace to provide the
required return air.
Downflow models draw the return air from the
top of the furnace.
The minimum
required
clearance to the top of the furnace is detailed
on the furnace rating plate. Additional clear-
ance may be required depending
upon filter
accessibility.
For each application, the U.S.A. home manufac-
turer shall comply with all of the following condi-
tions to have acceptable retum air systems for
closet installed forced air heating appliances:
a.
Regardless of the location, the return air
opening into the closet shall not be less
than specified in the appliance's listing.
b.
Means
shall
be provided
to prevent
inadvertent closure by a flat object placed
over the return air opening when it is
located in the floor of the closet (versus
the vertical front or side wall).
c.
The cross-sectional
area of the return
duct system leading into the closet shall
not be less than 390 square inches.
d.
The total free area of openings in the floor
or ceiling registers serving the return air
duct system must be at least 352 sq. in.
At least one register should be located
where it is not likely to be covered by
For
floor
return
systems,
the
manufactured home manufacturer shall
affix a prominent marking on or near the
appliance where it can be easily read
when
the closet
door
is open.
The
marking shall read:
CAUTION:
HAZARD
OF ASPHYXIATION:
Do not
cover or restrict
return air opening.
k.
Air conditioning
systems may require
more duct, register and open louver area
to obtain
necessary
airflow.
Use
NORDYNE's
certiduct
program
to
determine proper duct size for A/C.
AIR DISTRIBUTION
SYSTEMS
For proper air distribution,
the supply duct
system must be designed so that the static
pressure measured
external to the furnace
does not exceed the listed static pressure
rating shown on the furnace rating plate.
Three typical distribution systems are illustrated
in Figure 2. Location,
size, and number of
registers should be selected on the basis of
best air distribution and floor plan of the home.
A Single trunk duct
[]
carpeting, boxes and other objects ............................................................
e.
Materials
located
in the return
duct
system
must
have
a flame
spread
classification of 200 or less. This includes
a-closetdo0r if theefu-rnac_ is"fna-cios_t._
f.
Noncombustible panshaving 1"upturned
flanges are located beneath openings in
a floor duct system.
g.
Wiring
materials
located in the return
duct,system
shall conform_to
Articles ,-
300-22 of the National Electrical Code
(ANSI CI/NFPA-70).
h.
Gas piping is not run in or through the
return duct system.
i.
Test the negative pressure in the closet
with the air-circulating
fan operating at
high speed and the closet closed. The
negative
pressure
is to be no more
negative
than minus 0.05 inch water
column.
BJ Dual trunk duct
_
]
-
_ wlcrossover
connector-_-
J
U
U
U
Figure 2. Typical Supply Duct System
FLOOR CAVITY
U
(depth equal to "X* in F3gure 5 and Table 5)
t
JJJJJJJJJJJJJJJJJJJJJ
JJ _
J Ji_
x-l--- -----.._
i
l ,l
I
I)J
SuPPLYAiR
oucT
--
I_!
/
k
h\l
Figure 3. Floor Cavity Cut-Out
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

M2rc-100M2rl-060M2rl-100

Table of Contents