Leak Check; High Altitude Derate - Nordyne M2RC-080 Installation Instructions Manual

Direct vent (sealed combustion) forced air gas furnaces: m2rc series 90+ upflow and m2rl series 90+ downflow condensing furnace
Table of Contents

Advertisement

Typical Left Side Entry - Upflow
Burner Viewport
Roll_ut
Limit
°Ourn r
°'llll
Some Utilities
Assembly
Require Shut- I F
_
Off Valve to
be 4 to 5 feet
Above Floor
- Ground
/
Denotes field-
Automatic Gas Valve /
provided and
(wdh manuel shut-off)
installed
component.
Typical Right Side Entry - Downflow
Denotes field-
provided
and
Automatic
installed
Gas Valve
components.
(with manual
shut-off)
'
Ground J<
,
UrlioR
Burner
Roll-Out Lim_
Assembly
_,
Ii .....
int
Some Utilities
1 Require Shut-
Off Valve to
be 4 to 5 feet
Above Floor
_-Bumer Viewport
Figure 21. Typical Gas Service Connection
NOTE:
Gas piping must not be run in or
through
air ducts,
chimneys,
gas vents,
elevator
shafts,
etc.
water column), the furnace must be discon-
nected from the gas supply piping system to
prevent damage to the gas control valve.
If the test pressure is less than or equal to
1/2 psig (14 in. water column), the furnace must
be isolated from the gas supply line by closing
the manual shut-off valve.
Leak Check
After the gas piping to the furnace is complete,
all connections must be tested for gas leaks.
To check for leaks use only a soap and water
solution or other approved method.
High Altitude Derate
The nameplate input rating for the furnaces
apply for elevations up to 2,000 feet (610m)
above sea level. For elevations
over 2,000
feet, reduce the input by 4% for each 1,000 feet
above sea level. For example, a furnace ap-
plied at an elevation of 5,000 feet should be
derated by 20%. See Table 9 describing the
correct orifice for derate.
NOTE: For Canadian high altitude (2,000 to
4,500 ft.), simply
reduce the gas manifold
pressure to 2.8" WC for natural gas and 8.5"
WC for LP gas without changing the orifices.
NOTE: The density
of air decreases
with
increasing elevation above sea level. This
reduces the quantity of combustion air drawn
into the furnace under normal operation and
requires the unit be derated by using smaller
gas orifices or lower manifold pressure.
Compounds
used on threaded joints of gas
piping must be resistant
to the actions
of
liquefied petroleum gases.
The main manual gas valve and main power
disconnect
to the furnace
must be prop-
erly labeled by the installer in case emer-
gency shutdown
is required.
CAUTION:
Do not use matches,
lighters,
candles,
or other sources
of open flame to check
for gas leaks.
NOTE:
When pressure testing gas supply
lines at pressures greater than 1/2 psig (14 in.
CAPACITY
OF BLACK IRON GAS PIPE (CU, FT, PER HOUR)
FOR NATURAL
GAS (SPECIFIC
GRAVITY
- 0.60)
i_OMI MAL
LENGTH
OF PIPE RUN
BLACK IRON
_feet)
PIPE DIAMETER
(in. I
10
2D
30
40
50
60
70
80
1/2
130
90
75
65
55
50
45
40
3#4
280
190
150
130
115
105
95
90
1
520
350
285
245
215
195
180
170
1 114
1050
730
590
5(0
440
400
370
350
1 1/2
1600
1100
890
7_
670
610
560
530
T_e cubicfeetperhourlietedinthetableabove mustbegreeterthan
the cubicfeetper hourofgas flowrequiredby thefurnace.
To determine the cubic feet per hour of gas flow required by the
furnace, divide the input rate ofthe furnace bythe heating value ofthe
gas:
Cubic Feet
--
InputTo Furnace (Btu/hr)
Per HourRequired
HeatingValue ofGas (Btu/Cu, Ft.)
Table 8. Capacity of Black Iron Gas Pipe
(cu. ft. per hour) for Natural Gas
(specific gravity = .60)
2O

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

M2rc-100M2rl-060M2rl-100

Table of Contents