6. Select the slot of the CP or the CPU.
Both methods are possible.
7. Connect using the "Connect" button.
The "Connect online" wizard guides you through the remaining steps in installation.
You will find further information on the online functions in the STEP 7 information system.
Downloading the firmware via the Web server of the CPU
Follow the steps below to connect to the Web server of the CPU from the engineering station
and to download the CP's new firmware file to the station.
Requirements in the CPU configuration
1. Open the corresponding project on the engineering station.
2. Select the CPU of the station involved in STEP 7.
3. Select the "Web server" entry.
4. In the parameter group "General", select the "Enable Web server for this interface"
option.
5. With a CPU version V4.0 or higher, create a user in the user administration with the
required rights.
You need to assign the right to perform firmware updates in the access level.
The procedure for establishing a connection to the Web server depends on whether you
have enabled or disabled the "Allow access only using HTTPS" option in the "General"
parameter group:
● Connection establishment with HTTP
Procedure if the "Allow access only using HTTPS" option is disabled
● Connection establishment with HTTPS
Procedure if the "Allow access only using HTTPS" option is enabled
These two variants are described in the following sections.
Requirement: The new firmware file is stored on your engineering station.
You will find the requirements for access to the Web server of the CPU (permitted Web
browser) and the description of the procedure in the STEP 7 information system under the
keyword "Information about the Web server".
Connection establishment with HTTP
1. Connect the PC on which the new firmware file is located to the CPU via the Ethernet
interface.
2. Enter the address of the CPU in the address box of your Web browser: http://<IP
address>
3. Press the Enter key.
The start page of the Web server opens.
CP 1243-7 LTE
Operating Instructions, 04/2017, C79000-G8976-C381-03
Diagnostics and upkeep
6.3 Loading firmware
125