Sub
Error Code
Code
1
Abnormal Hot water outlet thermistor (Open)
E407
2
Abnormal Hot water outlet thermistor (Short)
1
Abnormal Cold water inlet thermistor (Open)
E421
2
Abnormal Cold water inlet thermistor (Short)
1
Abnormal Cold water inlet2: thermistor (Open)
E432
2
Abnormal Cold water inlet2: thermistor (Short)
1
Abnormal water adjustment valve. (Open)
E434
2
Abnormal water adjustment valve. (Close)
E438
0
Abnormal circulation pump. ("A" models only)
E439
0
Abnormal flow sensor
1
Abnormal Hot water inlet2: thermistor(Open)
E441
2
Abnormal Hot water inlet2: thermistor(Short)
1
Abnormal mixing valve(Open)
E445
2
Abnormal mixing valve(Close)
1~7
Abnormal communicatin between PCB and Ignitor.
Abnormal communication between PCB and
8
Ignitor
9
Abnormal communication between PCB and FAN
E515
10
Abnormal monitoring device of PCB
Abnormal communication between PCB and Dual
11~12
Venturi
E517
0
Abnormal dip switch setting
E593
1
Abnormal panel key
Abnormal input data from High limit switch of Heat
0
exchanger
1
Abnormal input data from exhaust sensor
E594
2
Abnormal input data from flame rod
3~14
Abnormal memory of PCB
15
Below the range of input data from Pressure sensor
16
Over the range of input data from Pressure sensor
74
NPE Service Manual
Function
Self-diagnostic/Action
Check the thermistor.
●
Replace the thermistor.
●
Check the thermistor.
●
Verify [C] value in DIAGNOSTIC mode.
●
Replace the thermistor.
●
Check the thermistor.
●
Check thermistor voltage and resistance values.
●
Replace the thermistor.
●
Check the water adjustment valve.
●
Check the circulation pump.
●
Check water filter for blockage.
●
Check the flow sensor.
●
Check the cold water main line.
●
Set to Internal Recirculation mode and verify flow rate.
●
Check the flow sensor.
●
Check the thermistor.
●
Replace the thermistor.
●
Check the mixing valve.
●
Check the PCB.
●
Check the PCB connection.
●
Check the Ignitor.
●
Check the PCB connection.
●
Check the Fan.
●
Check the PCB connection.
●
Check the Dual Venturi.
●
Check the PCB connection.
●
Check the Dual Venturi.
●
Check the dip switches on the front panel and PCB.
●
Check the Panel.
●
Check the PCB.
●
Check the exhaust sensor wiring connection.
●
Check the exhaust sensor.
●
Check the flame rod wiring connection.
●
Check the flame rod.
●
Check the PCB
●
Check the Pressure sensor wiring connection.
●
Check the output voltage of pressure sensor.
●
Version 2.21