Roberts Gorden HF 30 v4 Installation, Commissioning, Service & User Instructions page 13

Combat
Table of Contents

Advertisement

CABINET HEATER
Table 2.4
Ecoflam ON/OFF Natural Gas (G20) Dungs Valve, Burner
Reference C
Data for all versions "H" horizontal, "HF" high flow
Gas rates corrected to standard conditions 1013.25 mbar 15°C
INLET PRESSURE 20 m ba r
M ODEL
Gross heat input
Net heat Input
A pprox heat output
Start Gas Orif ice
Max Gas Rate
Main Burner Gas Pres sure
Start Gas Pressure
BURNER TYPE
Burner Head
Burner Injec tor
Head Setting
1s t Flame A ir Setting
2nd Flame A ir Setting
Gas V alve Setting
V alve Type
Main Gas
V alve Type
Start Gas
A IR PRESSURE SWITCH
SETTING
Max f lue static pres sure
norm. f lue static pres sure
Gas Connec tion
S.= S.I T
H.= HONEY WELL
(Minim um 17 m ba r, Ma x im um 25 m ba r)
PGP 015 PGP 020 PGP 030 PGP 040 PGP 050 PGP 060 PGP 070 PGP 080 PGP 0100
(kW)
56.1
73.7
(kW)
51
67
(kW)
46.9
60.3
(mm dia.)
3
(Sm
/hr)
5.4
7.1
(mbar)
4.7
2.5
(mbar)
N/A
N/A
A ZUR
BLU
60
120
s
s
(mm)
0
10
3.5
3.9
MBDLE
MBDLE
405
405
(mbar)
3.8
4.5
(mbar)
-0.05
-0.05
3/4"
3/4"
103
144.7
182.1
93.6
131.5
165.5
81.9
114.7
144.8
5.0
6.0
9.9
13.9
17.5
4.9
5.2
8.5
N/A
1.8
2.8
BLU
BLU
BLU
120
170
250R
s
s
s
11
15
14
8
2.8
5.1
MBDLE
MBDLE
MBDLE
405
407
410
S
S
0 832 051 0 832 051 0 832 051 0 832 051 0 832 051 0 832 051
5.9
2.9
5.5
-0.09
-0.30
-0.05
3/4"
3/4"
1 1/4"
220
253.6
297
200
230.5
270
176
202.8
237.6
7.0
7.0
7.0
21.2
24.4
28.6
5.6
7.5
9.5
0.9
1.1
1.7
BLU
BLU
BLU
250
250
250S
s
s
s
24
24
24
3.3
5.3
2
MBDLE
MBDLE
MBDLE
410
410
410
S
S
S
3.6
4.5
6.8
-0.25
-0.17
0.10
1 1/4"
1 1/4"
1 1/4"
363
330
290.1
7.0
34.9
11
3.4
BLU
350
s
21
2
MBDLE
412
S
5.1
0.45
1 1/4"