Roberts Gorden HF 30 v4 Installation, Commissioning, Service & User Instructions page 12

Combat
Table of Contents

Advertisement

CABINET HEATER
Table 2.3
Burner Reference "G"
M ode l
He at Input (gr os s )
Kw
Btu/hr
Nom inal He at output
Kw
Btu/hr
Ecoflam Bur ne r type
Nozzle Size
Us gall/hr
Angle & Type
M ak e
mm
He ad s e tting
Air s e tting
Number
Bur ne r fue l
Bar
pr e s s ur e
PSI
Fue l
L/hr
cons um ption
imp gall.hr
M ax. oil pr e s s ur e
Bar
to pum p inle t
PSI
Oil Fired Burner Data (Ecoflam Burner)
POP 015 POP 020
POP 030
51
73.6
109.7
174012
251073
374277
44
58.6
87.9
150000
200000
300000
Minor 8
Minor 8
Minor 12
1.00
1.50
2.25
60S
60S
60S
Danf oss Danf oss
Danf oss
8
0
14
4.2
8.5
5.5
12
10.3
10.3
175
150
150
4.82
6.96
10.37
1.06
1.53
2.28
0.21
0.21
0.21
3
3
3
POP 040
POP 050
POP 060
146.2
183.2
221.2
498786
625000
754870
117.2
146.5
175.8
400000
500000
600000
Minor 20
Minor 20
Minor 30
3.00
3.00
4.00
60S
60S
60A
Danf oss
Danf oss
Delevan
8
8
(Fully back)
(Fully back)
(Fully back)
2.5
4
3.7
10
13.8
12.4
145
200
180
13.83
17.32
20.92
3
3.81
4.6
0.21
0.21
0.21
3
3
POP 070
POP 080
256.2
300.6
874060
1025647
205.2
234.5
700000
800000
Minor 30
Minor 30
5.00
5.50
60A
60A
Delevan
Delevan
8
8
8
(Fully back)
(Fully back)
4.5
6.2
10.7
10
155
145
24.23
28.43
5.33
6.25
0.21
0.21
3
3
3
POP 0100
355.8
1213874
293.1
1000000
Major 30
7.00
60A
Delevan
(Fully
Forw ard)
1.8
11
160
33.65
7.4
0.21
3

Hide quick links: