Center Of Gravity Location - York PCG6B42 Installation Manual

Pcg6 series single package air conditioner / gas heat 3 thru 5 tons -208/230v - 3 phase
Hide thumbs Also See for PCG6B42:
Table of Contents

Advertisement

5285473-UIM-E-1217
5. Roof structures must be able to support the weight of the unit and
its options/accessories. Unit must be installed on a solid, level roof
curb or appropriate angle iron frame.
6. Maintain level tolerance to 1/8" across the entire width and length of
unit.
CLEARANCES
WARNING
!
Do not permit overhanging structures or shrubs to obstruct con-
denser air discharge outlet, combustion air inlet or vent outlets.
All units require particular clearances for proper operation and service.
Installer must make provisions for adequate combustion and ventilation
air in accordance with section 5.3 of Air for Combustion and Ventilation
of the National Fuel Gas Code, ANSI Z223.1 – Latest Edition (in
U.S.A.), or Sections 7.2, 7.3, or 7.4 of Gas Installation Codes, CSA-
B149.1 (in Canada) - Latest Edition, and/or applicable provisions of the
local building codes. Refer to Table 4 for clearances required for com-
bustible construction, servicing, and proper unit operation.
Table 2: Weights and Dimensions
Weight (lbs.)
Model
Shipping
36065
466
36100
473
42065
500
42100
502
48065
520
48100
528
48125
533
60065
537
60100
541
60125
548
FIGURE 2: Center of Gravity Location
4
Center of Gravity
Operating
X
461
28
468
28
495
28
497
28
515
28
523
28
528
28
532
29
536
28
543
27
COMPRESSOR
"A"
FRONT
OF UNIT
X
RIGGING AND HANDLING
CAUTION
!
If a unit is to be installed on a roof curb other than a Unitary Products
roof curb, gasket or sealant must be applied to all surfaces that come
in contact with the unit underside.
CAUTION
!
All panels must be secured in place when the unit is lifted.
The outdoor coils should be protected from rigging cable damage
with plywood or other suitable material.
Exercise care when moving the unit. Do not remove any packaging until
the unit is near the place of installation. Rig the unit by attaching chain
or cable slings to the lifting holes provided in the base rails. MAKE
SURE to use the spreader bars across the top of the unit if the length of
the spreader bars exceed the largest dimension across the unit.
CAUTION
!
Before lifting, make sure the unit weight is distributed equally on the
rigging cables so it will lift evenly.
Units may be moved or lifted with a forklift. Slotted openings in the base
rails are provided for this purpose.
4 Point Load Location (lbs.)
Y
A
15
161
15
163
15
175
15
176
15
189
15
169
15
164
15
174
15
177
15
151
"D"
CENTER OF
GRAVITY
"C"
"B"
Y
A0295-001
B
C
113
96
114
101
123
104
124
101
116
93
139
115
145
124
142
124
140
117
167
141