Requesting an Echo Profile
a.
In PROGRAM mode, navigate to:
LEVEL METER > DIAGNOSTICS >
ECHO PROFILE (3.1)
b.
Press R R IGHT arrow
profile.
c.
In the Profile screen, press U U P
arrow
to select the T T ransmit
icon, and R R ight ARROW
update the profile.
d.
Press D D OWN arrow
the E E xit icon, then R R ight ARROW
to return to previous menu.
Device Address
The default address for the device is 0. To reset the address via the handheld
programmer, see
Device Address
Auto False Echo Suppression
If SITRANS LR260 displays a false high level, or the reading is fluctuating between the
correct level and a false high level, you can use the Auto False Echo Suppression
parameters to prevent false echo detection. See
setup (TVT SETUP)
for instructions.
Page 30
SITRANS LR260 (HART) – INSTRUCTION MANUAL
DIAGNOSTICS
ECHO PROFILE
MEAS. VALUES
REMAIN. DEV. LIFE
to request a
REMAIN. SENS. LIFE
to
to select
transmit icon,
selected
on page 76.
2.2.5. TVT (Auto False Echo Suppression)
3.1
transmit icon,
deselected
exit icon,
selected
exit icon,
deselected
7ML1998JE01