Panasonic S-36PU1E5 Technical Data & Service Manual page 190

R410a inverter, indoor/outdoor units, 4-way cassette, ceiling, wall mounted, low shilhouette ducted, ducted
Table of Contents

Advertisement

1
Refrigerant charging
For the twin connection, the amount of refrigerant required for pipe length 30m has been included in this unit at the factory
while that required for pipe length 20m has been included for the triple/double-twin connections.
No additional charge is required for the first 30m pipe length in the case of the twin connection and for the first 20m in the case
of the triple/double-twin connections. The amount of included refrigerant for each model is listed on NAME PLATE.
Make additional charges by adding up pipe length in an order of main pipe (L)
and then selecting the amount of refrigerant corresponding to the remaining (after 30m for the twin connection and after 20m
for the triple/double-twin connections) liquid side pipe diameter and pipe length from the below table.
Liquid pipe diameter
ø6.35
ø9.52
Wiring
Earth
L
N
Controll
cable
U1
U2
R1
R2
Indoor unit
(DOUBLE TWIN type)
SG : Shows the earth for the shielded cable.
Addition amount of refrigerant [g/m]
20
50
Earth
Earth
L
L
N
N
Controll
cable
U1
U1
U2
U2
R1
R1
R2
R2
Indoor unit
Indoor unit
(TRIPLE type)
branch pipe (La
Power supply
(220/230/240V~)
Circuit breaker
Switch
Earth
Controll
L
cable
N
Controll
cable
U1
U2
R1
R2
Indoor unit
Wired remote
controller
1-184
Lb
Lc wide diameter)
Power supply
(220/230/240V~)
(380/400/415V 3N~)
Circuit breaker
Circuit breaker
Switch
L
L1
N
L2
L3
Earth
N
Outdoor unit
U1
U2
Outdoor unit
Power supply
Switch
Earth