Reconfiguring Outdoor Control using
®
iComfort Wi-Fi
Thermostat
If any component of the HVAC system is changed, ( e.g. an
outdoor sensor is replaced), reconfigure the system. To
begin reconfiguring a system, select the Setup tab.
System Overview
Refer to the iComfort Wi-Fi
configuration procedures.
IMPORTANT
Some scroll compressors have internal an vacuum
protector that unloads the scrolls when suction pressure
drops below 20 psig. A hissing sound is heard when the
compressor is running unloaded. Protector resets when
low pressure in system is raised above 40 psig. DO NOT
REPLACE COMPRESSOR.
The outdoor control provides the following functions:
Demand defrost algorithm
Field-selectable defrost termination temperatures
through the thermostat interface
Internal switching of outputs
Anti-short-cycle
delay
thermostat interface
Five-strike lockout function
Ambient (RT13), coil (RT21) and liquid line (RT36)
temperatures monitoring and protection
COMPRESSOR PROTECTION — FIVE-STRIKE
LOCKOUT FUNCTION
The five-strike lockout function is designed to protect the
unit's compressor from damage. The five-strike feature is
used for high (S4) and low (S87) pressure switch trips.
Resetting Five-Strike Lockout
Once the condition has been resolved, power to the outdoor
control R terminal must be cycled OFF.

Diagnostic Information

The following diagnostic information is available through the
thermostat user interface. Refer to the Wi-Fi
System Setup Guide.
Compressor anti-short cycle delay timer status
Cooling rate
Heating rate
Compressor shift delay timer status
Defrost status
High pressure switch status
®
Thermostat Installer Guide for
(adjustable
through
®
Installer
Low pressure switch status
Compressor top cap switch status
Liquid line temperature
Outdoor ambient temperature
Coil temperature
Time since last defrost
Calibration delta T
Current delta T
Outdoor fan RPM
Compressor active alarm
Compressor Hz
Inverter compressor short cycle
Heat sink temperature

Installer Test

Verify the proper operation of the system by running the
Installer Test feature through the thermostat interface. Refer
to the iComfort Wi-Fi

Defrost Function

The outdoor unit control measures differential temperatures
to detect when the system is performing poorly because of
the
ice build-up on the outdoor coil. The controller self-calibrates
(see figure 33) when the defrost system starts and after each
system defrost cycle. The outdoor unit control monitors
ambient temperature, outdoor coil temperature, and total
run-time to determine when a defrost cycle is required. The
coil temperature sensor is designed with a spring clip to
secure the sensor to the outside coil tubing. The location of
the coil sensor is important for proper defrost operation (see
figure 59 on page 77 for location of coil sensor).
NOTE - The outdoor unit control accurately measures the
performance of the system as frost accumulates on the
outdoor coil. This typically translates into longer running time
between defrost cycles as more frost accumulates on the
outdoor coil before the outdoor control initiates defrost
cycles.
DEFROST OPERATING MODES
The outdoor control has three operational modes:
Defrost calibration (see figure 33)
Operation
Defrost test
DEFROST TERMINATION TEMPERATURES
The defrost termination temperature setting selections (50,
70, 80, 90, and 100°F) are available through the thermostat
interface. The factory default setting is 50°F (10°C).
NOTE - Colder climates may require a higher discharge
termination temperature setting to maintain a clear coil.
Page 43
®
Installer's System Setup Guide.