Typical Reversing Valve Components And Operation - Lennox XP25-024-230-01 Installation And Service Procedure

Dave lennox signature collection xp25 series units
Table of Contents

Advertisement

SOLENOID
TO COMPRESSOR
DISCHARGE LINE
LINE TO OUTDOOR
COIL
SUCTION LINE (TO
COMPRESSOR)
VAPOR LINE (TO SERVICE VALVE)
IMPORTANT - CONFIRM CORRECT CONNECTIONS OF
REFRIGERANT LINES TO REVERSING VALVE BEFORE
BRAZING IN VALVE.
STATUS CODE:
Diagnostic screen in room thermostat indicates when reversing valve is ON.
ERROR CODES:
There is no feedback from the reversing valve to the outdoor control therefore no error codes is displayed on the outdoor
®
control or iComfort Wi-Fi
shut down by other controls.)
IMPORTANT - ENSURE NEW REVERSING VALVE IS INSTALLED EXACTLY AS ORIGINAL
VALVE.
Figure 39. Typical Reversing Valve Components and Operation
room thermostat. (NOTE - If the reversing valve does not operate as designed, the system is
1.
WHEN THE SOLENOID IS ENERGIZED (ON), THE
EVAPORATOR (INDOOR COIL – E) REFRIGERANT
PRESSURE IS DIRECTED TO THE SUCTION (S) BACK
TO THE COMPRESSOR.
2.
WHEN THE SOLENOID IS DE-ENERGIZED (OFF),
REFRIGERANT PRESSURE IS DIRECTED FROM THE
CONDENSER (OUTDOOR COIL – C) TO THE SUCTION
(S) BACK TO THE COMPRESSOR.
Page 61
REVERSING VALVE
OPERATION
XP25