LG FMN0760NL Service Manual page 83

Free joint multi type
Table of Contents

Advertisement

Product doesn't operate with the remote controller.
Trouble 2
Turn on main power.
While the compressor has been stopped, the compressor does not operate
owing to the delaying function for 3 minutes after stopped.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the low speed as force).)
Caused by other parts except
Caused by the remote controller.
the remote controller
When the mark (
) is displayed in LCD
Check the contact of CN-DISP 1 connector
screen, replace battery.
When the detect switch (double key) inside the
Check DISP PWB Ass'y
remote controller door is fault, it is impossible to
-Voltage between CN1
-
: DC +5V
operate temperature regulating(L / M) and wind
speed selecting.
Check point
• Check the connecting circuit between
Check the connecting circuit between the
MICOM PIN
remote controller MICOM(No.27)-R02L(10K),
• Check receiver ass'y
R01L(1K), C01L(680pF)
-83-