Chapter 4
[AA111]~[AA115][bb-40]

RUN command selection

Code/Name
AA111
RUN command
00~03
input source
selection,
1st-motor
*1) 00([FW]/[RV] terminal)/01(3-wire)/02(Keypad's RUN key)/03(RS485)
・Select in which way will be operated.
In case it does not work, please review it.
Keypad keys settings
Code/Name
AA-12
RUN key of
keypad rotation direction,
1st-motor
AA-13
STOP key enable
at RUN command from
terminal , 1st-motor
・[AA-12] specifies in which direction (forward/reverse)
will be the rotation after pressing the RUN key in the
operation keypad.
・[AA-13] changes the operation of the STOP key.
Independently of the actual setting of the STOP key it
performs a stop. The STOP circumstances can be
changed only by the setting selected in [AA-13],
RUN command direction restriction
Code/Name
AA114
RUN direction
restriction,1st-motor
・It will avoid that the output goes over the imposed
limitation in case of a mistaken operation.
Restart operation after decel/free-run STOP
Code/Name
AA115
00(Deceleration stop)/
STOP mode
01(Free-run stop)
selection, 1st-motor
00(Start with 0Hz)/
01(Start with frequency
bb-40
matching)/
Restart mode after FRS
02(Start with Active
release
frequency matching)/
03(Detect speed)
・For when a stop command is executed, deceleration
stop or free-run stop can be selected.
・If input terminal 032[FRS] is active (ON), free-run stop is
possible.
・With [bb-40], a restart with the release of the [FRS], or a
restart operation that will be executed after the full
stop of the free-run can be selected.
・In free-run stop it can be configured to stop by inertia if
the [E007] overvoltage error occurs during deceleration
(The torque will be lost).
Range (unit)
Initial value
02(JPN)/
00(EU)
(USA)
(ASIA)
(CHN)
Range (unit)
Initial value
00(Forward)/
00
01(Reverse)
00(Disable)/01(Enable)/
01
02(Enable only at trip)
.
Range (unit)
Initial value
00(No restriction)/
01(Only forward)/
00
02(Only reverse)
Range (unit)
Initial value
00
00
For parameter configuration

Control mode selection

Code/Name
AA121
Control mode
00~03, 08, 09, 11 *2)
selection,
1st-motor
*2) IM control: 00([V/f] constant torque)/01([V/f] reduced torque)/
02([V/f] Free V/f)/03([V/f] constant torque with Automatic-trq boost)/
08(Sensorless vector control)/
09(0Hz-area sensorless vector control)/
SM/PMM control: 11(Sensorless vector control (SM/PMM))
・Generally for a light duty control (such as fans or pumps),
the [V/f] control with constant torque or the [V/f]
control with reduced torque are more closer to the
operation characteristics of fans and pumps.
・For heavy duty (Cranes, etc...), sensorless vector
control is the typically used. In the case there is an
encoder, use the vector control with encoder.
・For a magnet motor select the sensorless vector control
(SM/PMM).
※ With a standard duty (ND) all the options are available,
but for Light and Very Light duty (LD/VLD) the option
09 is not available.
Vector control with encoder mode
Code/Name
AA123
00(Speed/Torque control mode)/
01(Pulse train position control)/
Vector
control
02(Position control)/
mode selection,
03(High-resolution position control)
1st-motor
・For Vector control with encoder ([A121]=10) select
Speed/Torque control (00) or Position control (02).
・For more information, refer to the user's guide.
2nd motor When Intelligent Input terminal 024[SET] is enabled.
Code/Name
AA201 Main speed input source selection,
2nd-motor
AA202 Sub speed input source selection,
2nd-motor
AA204 Sub speed setting, 2nd-motor
Calcuration symbol selection
AA205
for speed reference,
AA206 Add frequency setting, 2nd-motor
AA211 RUN-command input source
selection, 2nd-motor
AA214 RUN-direction restriction selection,
1st-motor
AA215 STOP mode selection, 1st-motor
AA221 Control mode selection 2nd-motor
AA223 Vector control mode selection,
2nd-motor
4-14
[AA121]~[AA223]
Range (unit)
Initial value
Range (unit)
Initial value
Range
(unit)
Same as AA101
Same as AA102
Same as AA104
Same as AA105
2nd-motor
Same as AA106
Same as AA111
Same as AA114
Same as AA115
Same as AA121
Same as AA123
00
00
Initial
value