[WIRING PRECAUTIONS]

If there are high levels of noise, ground the AG terminal and FG terminal with
Class D grounding (Class 3 grounding) or higher dedicated for the PLC.
Failure to observe this could lead to malfunctioning.
When wiring in the PLC, be sure that it is done correctly by checking the product's
rated voltage and the terminal layout. Connecting a power supply that is different
from the rating or incorrectly wiring the product could result in fire or damage.
Tighten terminal screws to the specified torque.
If a terminal screw is not tightened to the specified torque, it the module may fall
out, short circuit, or malfunction.
If a terminal screw is tightened excessively, exceeding the specified torque, the
module may fall out, short circuit, or malfunction due to breakage of the screw or
the module.
Be careful not to let foreign matters such as sawdust or wire chips get inside the
module. These may cause fires, failure or malfunction.
[STARTUP/MAINTENANCE PRECAUTIONS]
When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfunction.
Before starting cleaning or terminal screw retightening, always switch off the
power externally in all phases.
Not switching the power off in all phases can cause a module failure or
malfunction.
Never disassemble or modify the module.
Failure to observe this could lead to trouble, malfunctioning, injuries or fires.
Always turn the power OFF before installing or removing the module. Failure to
observe this could lead to module faults or malfunctioning.
Do not install/remove the terminal block more than 50 times after the first use of
the product. (IEC 61131-2 compliant)
[PRECAUTIONS FOR DISPOSAL]
Dispose of this product as industrial waste.
CAUTION
DANGER
CAUTION
CAUTION