Fujitsu AR*G45LHTA series Technical Manual page 53

Duct type
Hide thumbs Also See for AR*G45LHTA series:
Table of Contents

Advertisement

PEAK CUT MODE
Operation that suppressed the current value can be performed by means of the following on-
site work. The air conditioner is set to the Peak cut mode when closing the contact input of a
commercial ON/OFF switch to a connector on the outdoor control PC board.
Circuit diagram example
z
Outdoor unit
control PC board
Connector
1
2
* Make the distance from the PC board to the connected unit within 10m.
Use the following parts and construct a circuit as shown above.
Input Signal···ON : Peak cut mode, Input Signal···OFF : Normal operation
*To set the "Peak cut mode" level, refer to "13.FUNCTION SETTINGS".
Input Signal
Peak cut mode
Parts (Optional)
z
Parts name
Model name
Connected unit
Ex.) Switch
*10m
Signal
Field supply
ON
OFF
ON
OFF
External connect kit
UTY-XWZXZ3
Contact capacity : 24VDC or more, 10mA or more.
- (02 - 18) -