Fujitsu AR*G45LHTA series Technical Manual page 29

Duct type
Hide thumbs Also See for AR*G45LHTA series:
Table of Contents

Advertisement

(5) Press the TIMER SET button to confirm the setting. Press the TIMER SET button for a few seconds until the setting value stops
flashing. If the setting value display changes or if "- -" is displayed when the flashing stops, the setting value has not been set correctly.
(An invalid setting value may have been selected for the indoor unit.)
(6) Repeat steps 2 to 5 to perform additional settings. Press the SET TEMP. buttons (
again for more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled
after 1 minute if no operation is performed.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
• After turning off the power, wait 30 seconds or more before turning on it again. The Function Setting will not become active
unless the power is turned off then on again.
CONTENTS FUNCTION SETTING
• Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed
condition.
After the power is turned on, perform the Function Setting on the remote control.
• The settings may be selected between the following two: Function Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are selected.
1)
2)
3)
4)
5)
6)
7)
8)
9)
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Setting description
Standard (2500 hours)
Long interval (5000 hours)
Short interval (1250 hours)
No indication
2) Room temperature control for cooling
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
Setting description
Higher control
Slightly lower control
Lower control
Filter sign
Room temperature control for cooling
Room temperature control for heating
Auto restart
Room temperature sensor switching
Cool air prevention
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Function number
Function number
Standard
- (01 - 26) -
) (
) and FAN control button simultaneously
!
CAUTION
(  ... Factory setting)
Setting value
00
01
11
02
03
(  ... Factory setting)
Setting value
00
01
30
02
03

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ar*g54lhta seriesAo*g45letl seriesAo*g54letl series

Table of Contents