External Input & Output; External Input - Fujitsu AR*C45LCTU series Technical Manual

Duct type
Table of Contents

Advertisement

12.
EXTERNAL INPUT & OUTPUT
Input
Low noise mode
Peak cut mode
12-1.

EXTERNAL INPUT

ON/OFF of the "Low noise mode" and "Peak cut mode" functions can be specified by external
signal.
LOW NOISE MODE
The following reduces the operating sound of the outdoor unit from the normal sound.
The air conditioner is set to the "Low noise mode" when closing the contact input of a commercial
timer or ON/OFF switch to a connector on the outdoor control PC board.
* Performance may drop depending on the outside air temperature condition, etc.
Circuit diagram example
z
Outdoor unit
control PC board
Connector
1
2
* Make the distance from the PC board to the connected unit within 10m.
Use the following parts and construct a circuit as shown above.
Input Signal∙∙∙ON : Low noise mode, Input Signal∙∙∙OFF : Normal operation
* Set the "Low noise mode" level, refer to "13.FUNCTION SETTING".
Input Signal
Low noise mode
Parts (Optional)
z
Parts name
Model name
Output
Error status
Compressor status
Connected unit
Ex.) Switch
*10m
Signal
Field supply
ON
OFF
ON
OFF
External connect kit
UTY-XWZXZ3
Connector
CN10
CN11
CN12
CN13
Contact capacity : 24VDC or more, 10mA or more.
- (02 - 15) -
Remarks
See external
input/output settings
for details.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ar*c54lctu seriesAo*a45lctl seriesAo*a54lctl series

Table of Contents