Installing/mounting
4.4 Mounting the Power Modules
Drilling dimensions and cooling air clearances
Table 4-2
Frame
size
FSD
FSE
FSF
You can mount the Power Modules without any lateral cooling air clearance. For tolerance reasons,
1)
we recommend a lateral clearance of approx. 1 mm.
4.4.2

Hoisting gear

Use crane lifting lugs and the appropriate hoist‐
ing gear when mounting Power Modules.
Power Module weights:
32
Drilling dimensions, cooling air clearances [mm] and fixing [Nm]
Drilling dimensions
h
b
430
170
509
230
680
270
Technical data (Page 57).
Cooling air clearances
c
Top
Bottom
15
300
350
11
300
350
13
300
350
Hardware Installation Manual, 11/2016, A5E37800827C AB
Fixing
1)
Front
Screws/torque
100
4 x M5 / 6
100
4 x M6 / 10
100
4 x M8 / 25