Mount the sensor to the bracket using the enclosed Allen key (M8 x 20 mm), and tighten the
screws properly (max. 12 Nm).
4.5
Vibrations
Locate the sensor as far away as possible from components that generate mechanical vibration
in the pipe. Or separate from vibration generating components using flexible connections so that
there is no direct connection to them.
4.6
Cross talk
If more sensors are located close to each other, i.e. in the same pipe section, the meters may
disturb each other, especially at low flow. To prevent cross talk, connect the sensors with a
flexible connection instead of a permanent connection.
Avoid mounting the sensors on the same steel frame-insulate the meters individually on
separate mounting frames supported with rubber pads.
14
1
2
SFIDK.PS.028.S2.02
3
4