Bryant 619P Series Installation Instructions Manual page 9

High wall ductless split system sizes 09 to 30
Hide thumbs Also See for 619P Series:
Table of Contents

Advertisement

4
Always take precautions to protect the pipe when drilling
using a metal grid, a metal plate or other protective material.t
Alternate Connection Method for Power and Communication
Wiring (May not prevent communication wiring interference)
The main power is supplied to the outdoor unit. The field supplied
connecting cable from the outdoor unit to indoor unit consists of
four (4) wires and provides the power and communication signals
for the indoor unit. Two conductors are for power wiring (L1/L2,
or L/N), one is a ground wire, and one is a DC communication
wire.
Consult your local building codes and the NEC (National
Electrical Code) or CEC (Canadian Electrical Code) for special
requirements. All power wires must be sized per NEC or CEC and
local codes. Use Electrical Data table MCA (minimum circuit
amps) and MOCP (maximum over current protection) to correctly
size the wires and the disconnect fuse or breakers respectively.
Per caution note, only copper conductors with a minimum 300 volt
rating and 2/64--inch thick insulation must be used.
4
9
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

538p series

Table of Contents