Siemens RUGGEDCOM RX5000 Installation Manual page 43

Hide thumbs Also See for RUGGEDCOM RX5000:
Table of Contents

Advertisement

RUGGEDCOM RX5000
Installation Guide
Test
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
a
Siemens-specified severity levels
IEEE 1613 EMC Type Tests
NOTE
The RUGGEDCOM RX5000 meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports.
ESD
Radiated RFI
Fast Transient
EMC and Environmental Type Tests
Description
Magnetic Field
Voltage Dips & Interrupts
Voltage Dips & Interrupts
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC Power Supply
Dielectric Strength
HV Impulse
Description
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Enclosure Ports
DC Power ports
AC Power ports
30% for 1 period, 60% for 50 periods
AC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
DC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Test Levels
10V
10V
100 A/m
1000 A/m for 1 s
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
100% for 5 periods,
100% for 50 periods
2.5 kV common, 1 kV
differential mode @1 MHz
2.5 kV common, 1 kV
differential mode @1MHz
2.5 kV common, 1 kV
differential mode @1MHz
30 V Continuous, 300 V for 1 s
30 V Continuous, 300 V for 1 s
10%
2 kV (Fail-Safe Relay output)
2 kV
2 kV
5 kV (Fail-Safe Relay output)
5 kV
5 kV
Test Levels
+/-2 kV, +/-4 kV, +/- 8 kV
+/-4 kV, +/-8 kV, +/-15 kV
35 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
Chapter 6
Certification
Severity
Levels
3
3
5
3
3
3
4
4
3
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

A6x30095836

Table of Contents