Connecting The Phone Line To The Panel With A Db-8 Cord (49-442); Mounting/Connecting An Ac Power Transformer - GE Advent Installation Instructions Manual

Commercial fire system
Table of Contents

Advertisement

R J - 3 1 X
( C A - 3 8 A )
P H O N E J A C K
B R N
G R Y
O R G
B L U
Y E L
B L K
G R N
R E D
T E L C O
P R O T E C T O R
B L O C K
P H O N E
S P L I C E
( A )
( B )
W I R E
G R N
R E D
B L A C K
W H I T E O R Y E L L O W
G R N ( C )
R E D ( D )
Figure 18.Installing an RJ-31X Phone Jack
Connecting the Phone Line to the Panel
with a DB-8 Cord (49-442)
After installing the RJ-31X jack, you are ready to connect
the phone line to the panel.
To connect the DB-8 cord to the panel terminals and RJ-
31X jack:
1.
Insert one end of the DB-8 cord plug into the RJ-31X
(see Figure 19).
2.
Insert the other end of the DB-8 cord plug into the
phone jack on the Advent panel circuit board (see Fig-
ure 19).
3.
Check the phones on the premises for dial tone and the
ability to dial out and make phone calls. If phones do
not work correctly, check all wiring and correct where
necessary. Proceed to "Troubleshooting" on page 55 if
problems persist.
14
2 . 0 K O H M
E O L R E S I S T O R
4 9 - 4 6 7 o r 4 9 - 4 5 4
( F O R
O P T I O N A L
J A C K
T A M P E R )
T O P A N E L T E R M I N A L 1 1
T O P A N E L T E R M I N A L 1 2
( O R T O A N Y G E N E R A L P U R P O S E
I / O T E R M I N A L P R O G R A M M E D A S A N
I N P U T F O R O P T I O N A L J A C K T A M P E R )
T O
P R E M I S E S
P H O N E S
(PANEL CIRCUIT BOARD)
PHONE JACK
Figure 19.Connecting the DB-8 Cord to the Panel and
RJ-31X Jack
Mounting/Connecting an AC Power
Transformer
Use the following AC power transformer with Advent Fire
panels:
‰ 24 VAC output, 100 VA Class I, 110VAC, 60 Hz (60-830)
‰ 24 VAC output, 100 VA Class II, 110VAC, 60 Hz (60-823)
Line Carrier AC Power Transformer
Note
For UL 864 Advent Fire panel installations the 24 VAC,
100 VA Class I AC transformer is required.
1.
Mount the transformer in the cabinet at one of the two
locations shown in Figure 5.
Note
Transformer load (secondary) terminals must face the
center of the enclosure.
2.
Secure the transformer to the cabinet using the threaded
standoffs and supplied hex nuts.
3.
Route the AC power transformer cord or wires through
one of the knockouts.
Note
The AC supply is non-power limited. It must be separated
from all power limited wiring in the cabinet by at least 0.25"
and wired using a separate knockout.
DB-8 CORD
PLUG
BRN
GRY
RJ-31X
JACK
GRN
RED
8543268A.DSF
Advent Commercial Fire System