System Design and Installation
Maker
Model
OMRON
J7L-09
J7L-32
J7L-40
J7L-50
J7L-85
J7L-12
J7L-32
J7L-40
J7L-50
J7L-85
D Leakage Breakers
Select leakage breakers designed for inverters.
Since switching takes place inside the Servo Drivers, harmonic current leaks from the armature of the
motor. With inverter leakage breakers, harmonic current is not detected, preventing the breaker from
operating due to leakage current.
When selecting leakage breakers, remember to also add the leakage current from devices other than
the Servomotor, such as machines using a switching power supply, noise filters, inverters, and so on.
For details on leakage breakers, refer to the manufacturer's catalog.
The following table shows the Servomotor leakage current for each Servo Driver model.
Driver
R88D-WTA3HL to -WT02HL
R88D-WTA3H to -WT04H
R88D-WT05H to -WT10H
R88D-WT15H
R88D-WT20H/-WT30H
R88D-WT50H
R88D-WT60H/-WT75H
R88D-WT150H
Note 1. The above leakage current is for cases where Servomotor power line length is less than 10
meters. (It varies depending on the power line length and the insulation.)
Note 2. The above leakage current is for normal temperature and humidity. (It varies depending on
the temperature and humidity.)
3-26
Rated current
11 A
26 A
35 A
50 A
80 A
Two poles
12 A
Three poles
12 A
Two poles
25 A
Three poles
25 A
Two poles
35 A
Three poles
35 A
Two poles
45 A
Three poles
50 A
Two poles
65 A
Three poles
80 A
Leakage current (resistor/capacitor measurement)
(commercial power supply frequency range)
16 mA
8 mA
3 mA
5 mA
6 mA
9 mA
21 mA
57 mA
Coil voltage
200 V AC
24 V DC
Chapter 3