Panel; Parity; 20Ma Output; Default (Global Default) - Honeywell P531 Operating Manual

Flame monitor
Table of Contents

Advertisement

Panel

The front panel can be disabled for configuration
changes by entering a LOCK CODE. The lock code is
available
.
If panel is locked: All parameters are viewable but
none can be changed.

Parity

Using the UP and DOWN buttons, toggle between
parities for the RS-422 press then STORE to accept.
(Default is none)

20ma output

Using the UP and DOWN buttons, toggle between the
0 to 20 ma output or the 4 to 20 ma output then
STORE to accept. (Default is 4 to 20).

Default (global default)

To reset the system to default values:
Scroll to YES using the UP or DOWN buttons and
then press the STORE button. The STORE button
must be pressed again to answer the "are you sure?"
question.
All channels will be associated with the default viewing
heads, all channel set points will be defaulted, and all
viewing head parameters will be set to default values
(both Primary and Alternate). Channels will be set to 4
– 20 ma output mode.

FLAME RELAY CONTROL

The main flame relays are controlled by the Flame On
and Flame Off settings.
once the flame count has exceeded the Flame On
setting for Delay ON consecutive seconds.
versely the relays are de-energized once the flame
count has been less than Flame Off setting for FFRT
consecutive seconds. (See flowchart 4)

Flame On, Flame OFF

Hold either of these buttons for 2 seconds to enter the
relay menu.
Push the SELECT button at any time to change to the
next available channel.
Pushing the CHANNEL button will toggle between ALT
and PRIM settings (red display of Prim/Alt will indicate
parameter is currently active)
MODELS P531, P532 AND P532UI OPERATING MANUAL
The relays are energized
Con-
Pushing either the FLAME ON or FLAME OFF will
display the current set value in green.
Use the UP and DOWN buttons to change the settings
of these parameters and STORE to save the values.

Temperature display

See Configuration control charts 1 and 2
The temperature of a supported viewing head will be
displayed when the TEMP button is held for 2 sec-
onds. This display will also show the model of the
viewing head.
Certain versions of the S550 were produced without a
temperature sensor. These will display zero for tem-
perature.

AUTOMATIC SETUP

The flame monitor can be configured automatically in
two different ways. Seeing that this configuration is for
a specific channel it therefore falls under the channel
menu.
Only a currently selected channel can be set up
automatically, as indicated by a red Prim/Alt display

Fit

The auto fit menu is entered by selecting AUTOMATIC
from the channel menu.
The auto fit configuration only affects the gain of the
specific sensor selected and Flame On and Flame Off
set points).
A channel utilizing 2 simultaneous sensors (S550)
cannot be calibrated with this procedure.
It is necessary to have a flame present to use auto
set.
The gain will be set so that the flame count for the
specific sensor is between 1100 and 1300. The Flame
On will be set to 800 and Flame Off to 600.
If this is unobtainable, a message will be displayed
indicating the flame is too high or too low. (High flame
requires the installation of an orifice).
Note: If a channel is using two sensors a choice will
be given to turn one or the other of these sensors
off. The corresponding gain will be set to Zero for
S550 viewing heads or the sensor will be selected
for the specific channel for advanced viewing heads
Page 6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

P532uiP532

Table of Contents