Switching actuator, main module N 513/11
3x AC 230/400V, 20AX, C-load, load-check

Technical data

Power supply
• Bus voltage: supplied via the bus line
• Bus current, main module: typically 7 mA, max. 22 mA
main module + 4x submodule: typ. 11 mA, max. 26 mA
• Power dissipation: if all outputs = OFF: 0.2 W,
at max. load and all outputs = ON: approx. 3.5 W
Outputs
• 3 switching outputs, potential-free relay contacts:
- rated voltage: AC 230/400 V, 50/60 Hz
- rated current: 20 AX (200 µF) to DIN EN 60669-1,
20 A in AC1 mode (cos ϕ = 0.8) and 16A in AC3 mode
(cos ϕ = 0.45) as to DIN EN 60947-4-1,
- DC switching capacity: 20A at 24V DC
- Min. switching capacity: 100 mA at 12V AC
- Incandescent lamp load: max. 3,680 W
- LV halogen lamps, inductive transformer: 2,000 W
- LV halogen lamps, electronic transformer: 2,500 W
- Number of OSRAM ballasts for T5/T8:
QTI 1x28/54W: 56, QTP 1x36W: 31,
QT-M 1x26-42W:21, QTP 2x58W: 9,
QT-FQ 1x80W: 9
- Mech. lifetime: > 1,000,000 switching cycles
- Electr. lifetime: > 100,000 at AC1, > 30,000 at AC3
- Load current measuring range: 0.1...20,5 A, sinusoi-
dal
- Load current frequency range: 50/60 Hz, +/- 5 Hz,
- Measuring accuracy: +/- 9 % of the current measured
value and +/- 130 mA,
- Max. relay position changes per output and evenly
distributed per minute with simultaneous switching of
all relays: 20 with 3 outputs, 10 with 6 outputs, 7 with
9 outputs, 5 with 12 outputs, 4 with 15 outputs
Operating elements
• 1 commissioning push button:
for toggling between normal mode / addressing mode
• 1 push button:
for toggling between bus mode / direct mode
• 6 push buttons:
for direct operation (toggling) of up to 6 actuator out-
puts, independent of the bus
Display elements
• 1 red LED: for checking the bus voltage and for display-
ing normal mode / addressing mode
• 5 green LED: for display of the selected device
• 1 yellow LED: for displaying direct mode / bus mode
• 1 red LED per push button for direct operation:
for displaying whether the output is switched on or off
Siemens AG
Industry Sector, Building Technologies
Low Voltage Distribution
P.O. Box 10 09 53, D-93009 Regensburg
Connections
• Output circuits: screw-type terminals,
insulation strip length 7... 9 mm
The following conductor cross-sections are permitted:
- 0.5... 4.0 mm² single-core,
- 0.5... 2.5 mm² finely stranded without / with connec-
tor sleeve
Maximum torque for terminals: 0.5 Nm
• KNX bus line: bus terminal block
• Sub-module: 6-pole jack for bridging connector.
Mechanical data
• Housing: plastic
• Dimensions: DIN rail mounted device in N dimensions,
width 3 module units (1 module unit = 18 mm)
• Weight: approx. 240 g
• Fire load: approx. 3400 kJ
• Installation: Snap-on mounting on DIN rail
EN 60715-TH35-7.5
Electrical safety
• Degree of pollution (according to IEC 60664-1): 2
• Type of protection (according to EN 60529): IP 20
• Overvoltage category (according to IEC 60664-1): III
• Bus: safety extra-low voltage SELV DC 24 V
• Device complies with: EN 50090-2-2 and EN 60669-2-1
EMC requirements
• Complies with EN 50090-2-2, EN 50428 and
EN 60669-2-1
Environmental conditions
• Climatic withstand capability: EN 50090-2-2
• Ambient operating temperature: - 5 ... + 45 °C
• Storage temperature: - 25 ... + 70 °C
• Relative humidity (not condensing): 5 % to 93 %
Markings
• KNX EIB
CE mark
• In accordance with the EMC guideline (residential and
functional buildings), low voltage guideline
N 513/11, 6 pages
© Siemens AG 2010
Subject to change without further notice
GAMMA instabus
Technical product information
June 2010