Siemens N526E02 Technical Manual

Instabus switch/dimming actuator

Advertisement

Quick Links

Technical Specifications
Power supply
· Bus voltage: DC 29V (Class 2) via the bus line
· Bus current:: Notice: the device represents at least a
double bus load and takes up to 30 mA from the bus.
Outputs
· 8 outputs (latch relays, potential free contacts)
· rated voltage: AC 277 V, 50 ... 60 Hz
· rated current: 20 A, cos phi = 1
· switching current at AC 277 V: 0,1 ... 20 A, cos phi = 1
· DC switching current:
-
DC 10 ... 30 V: max. 16 A, resistive load
-
DC 230 V: max. 0,18 A, resistive load
· switching characteristic: to be set in parameter list (see
application program description)
Control voltage
· 1 ... 10 V (provided by dimmable ballast)
· in case of bus voltage failure: 10 V
Control power
· dimmable electronic ballast:
max 60 units
· signal amplifier:
max 12 units
CAUTION
There is no protection of the control circuits against de-
struction by accidental connection to mains voltage!
Operating elements
· 1 learning push button:
for toggling between normal mode/addressing mode
· 8 slide switches for manual operation
(slide in upper position: relay contact open = OFF,
slide in lower position: relay contact closed = ON)
Display elements
· 1 red LED:
for checking the bus voltage and for displaying normal
mode/addressing mode
· 8 slide switches for displaying the switching position per
channel (see above)
USA
Product and Applications Description
The switching/dimming actuator N 526E02 is a N-
system DIN-rail mounted device for controlling up
to eight groups (channels) of fluorescent lamps via
the DC 1-10 V control terminal of dimmable elec-
tronic ballasts (e.g. ECG-Dynamic-type from Osram).
In addition there is per channel a switching contact
for direct switching on/off of the connected fluores-
cent lamps. This contact can be operated manually
via a slide switch which also indicates the actual
switching state of the channel (when switching
manually as well as when switching via the bus). A
channel is switched on when the slide is in the
lower position.
Different functions can be configured per channel
such as for switching on/off fluorescent lamps,
dimming up / down or setting a particular dimming
level.
With the ETS (Engineering Tool Software) the appli-
cation program is selected, its parameters and ad-
dresses are assigned appropriately and downloaded
into the switching/dimming actuator.
One channel of the N 526E02 switching/dimming
actuator can control several dimmable electronic
ballasts. Their number is limited by the switching
capacity and by the control power. If the on/off
function is not used via the switching contact of the
switching/dimming actuator, the number of control-
lable ECGs is only dependent on the load of the DC
1-10 V control voltage. This might allow to control a
Connections
· load and control circuit, physical:
insulation strip length 8 ... 9 mm
permissible conductor types/cross sections:
-
0,5 ... 4 mm² single core
-
0,5 ... 2,5 mm² flexible conductor
· load circuit, electrical:
-
plain flexible conductor, min. 1 mm²:
current carrying capacity max. 6 A
-
flexible conductor with terminal pin,
crimped on gas tight, min. 1,5 mm²:
current carrying capacity max. 10 A
-
all other conductors, min. 1,5 mm²:
current carrying capacity max. 16 A
CAUTION
When looping through the L-conductor (connection blocks 1
and 2, 4 and 5, 7 and 8, 10 and 11, 13 and 14, 16 and 17,
19 and 20, 22 and 23), take care that the maximum connec-
tion current of 20 A (as governed by the maximum permissi-
ble printed conductor load) is not exceeded!
· Bus line:
-
pressure contacts on data-rail
-
screwless bus connection block,
Ø 0,6 ... 0,8 mm single core,
insulation strip length 5 mm
Physical specifications
· polymer casing
· N-system DIN-rail mounted device,
width: 8 MU (1 MU = 18 mm)
· weight: approx. 470 g (29oz)
· installation: rapid mounting on DIN rail complying with
EN 60715-TH35-7,5
Electromagnetic compatibility
complies with Part 15 of the FCC rules pursuant to the limits
for a Class A digital device
Environmental specifications
• ambient temperature operating: - 5 ... + 45° C (23...113°F)
• maximum ambient temperature range: - 25 ... + 70° C
(-13...158°F)
• relative humidity (non-condensing): 5 % to 93 %
instabus
Technical Manual
®
Switch/Dimming Actuator
N526E02
5WG1 526–1EB02
June 2015 / Page 1
larger number of ECGs (see Technical Specifications
below).
The power supply of the N 526E02 electronics is
provided via the bus (i.e. it requires no additional
power supply). When projecting an installation it
has to be considered that a N 526E02 represents a
double (and for short times even a triple) bus load
and takes up to 30 mA from the bus.
Application Programs
The switching/dimming actuator N 526E02 works
only together with the application program 25 A8
Switch-/ Dimm Actuator 981301. This new applica-
tion program contains several modifications and
new functions (e.g. an integrated 8-bit scene con-
trol). The application program can be loaded from
ETS2 V1.3 onwards.
Listings and Certifications
UL listed (E464611)
UL 916, Open Energy Management Equipment
CSA certified
CE marked
In accordance with the EMC guideline (residential and func-
tional buildings) and the low voltage guideline.
KNX / EIB certified
Markings
KNX, EIB, CE, UL
P.T.O.

Advertisement

loading

Summary of Contents for Siemens N526E02

  • Page 1 Technical Manual ® Switch/Dimming Actuator N526E02 5WG1 526–1EB02 June 2015 / Page 1 Product and Applications Description larger number of ECGs (see Technical Specifications below). The power supply of the N 526E02 electronics is The switching/dimming actuator N 526E02 is a N- provided via the bus (i.e.