Appendix A: Integration and Usage Tips

This section provides a list of useful information that is unique to the Intel
SR1625UR and should be kept in mind while integrating and configuring your Intel
Board S5520UR.
Only low-profile (1.2 in or 30.48 mm) DIMMs can be used in the server system.
Processor fans are not supported and are not needed in the server system. The system
fan module and power supply fans provide the necessary cooling needed for the system.
Using a processor fan in this system may cause Intel
incorrectly monitor the system fans.
The CPU air duct, air baffle, and DIMM Blanks must be used to maintain system
thermals.
To maintain system thermals, all hard drive bays must be populated with either a hard
drive or drive blank.
System fans are not hot-swappable
Use of the screw found on the front edge of the top cover is required when the unit is
installed in a user accessible environment.
The FRUSDR utility must be run to load the proper Sensor Data Records for the server
system onto the server board.
Make sure the latest system software is loaded on the server. This includes system
BIOS, FRUSDR, Integrated BMC firmware, and hot-swap controller firmware. The latest
system software can be downloaded
from
http://support.intel.com/support/motherboards/server/S5520UR/
Revision 1.5
Intel order number E47487-007
Appendix A: Integration and Usage Tips
®