Emerson Fisher C1 Instruction Manual page 5

Pneumatic controllers and transmitters
Table of Contents

Advertisement

Instruction Manual
D103292X012
Table 3. Bourdon Tube Pressure Range and Materials
(1,2)
PRESSURE RANGES
Bar
Psig
0 to 2.0
0 to 30
0 to 4.0
0 to 60
0 to 7.0
0 to 100
0 to 14
0 to 200
0 to 20
0 to 300
0 to 40
0 to 600
0 to 70
0 to 1000
0 to 100
0 to 1500
0 to 200
0 to 3000
0 to 350
0 to 5000
0 to 550
0 to 8000
0 to 700
0 to 10.000
1. If the process can trip to a pressure outside of the operating range of the sensing element, a commercially available device, such as an overpressure protector, may be used to protect
against pressure surges and pulsations.
2. Range marked on Bourdon tube may be in kPa (1 bar = 100 kPa)
3. Bourdon tube may be pressurized to limit shown without permanent zero shift.
4. With travel stop set at 110% of the range.
5. Bourdon tubes are also available in NACE compliant material. Contact your
Table 4. Bellows Pressure Ranges and Materials
Vacuum
Compound Pressure
Gauge Pressure
Positive pressure
(5)
Differential Pressure
1. If the process can trip to a pressure outside of the operating range of the sensing element, a commercially available device, such as an overpressure protector, may be used to protect
against pressure surges and pulsations.
2. Bellows may be pressured to limit shown without permanent zero shift.
3. Transmitter only.
4. Except transmitter.
5. The overrange limit for these sensing elements is a differential pressure equal to the maximum allowable static pressure limit.
Table 5. Supply Pressure Requirements
Output Signal Range
0.2 to 1.0 or 0 and 1.4 (differential gap)
Bar
0.4 to 2.0 or 0 and 2.4 (differential gap)
3 to 15 or 0 and 20 (differential gap)
Psig
6 to 30 or 0 and 35 (differential gap)
1. If this pressure is exceeded, control may be impaired.
MAXIMUM ALLOWABLE STATIC PRESSURE LIMITS
Standard
Bar
Psig
2.0
30
4.0
60
7.0
100
14
200
20
300
40
600
70
1000
100
1500
200
3000
350
5000
550
8000
700
10,000
Emerson Automation Solutions sales office
(1)
PRESSURE RANGES
0 to 150 mbar (0 to 60 inch wc)
0 to 340 mbar (0 to 10 inch Hg)
0 to 1.0 bar (0 to 30 inch Hg)
75 mbar vac. to 75 mbar (30 inch wc vac. to 30 inch wc)
500 mbar vac. to 500 mbar (15 inch Hg vac. to 7.5 psig)
1.0 bar vac. to 1.0 bar (30 inch Hg vac. to 15 psig)
0 to 150 mbar (0 to 60 inch wc)
(3)
0 to 250 mbar
(0 to 100 inch wc)
(4)
0 to 350 mbar
(0 to 140 inch wc)
0 to 0.35 bar (0 to 5 psig)
0 to 0.5 bar (0 to 7.5 psig)
0 to 0.7 bar (0 to 10 psig)
0 to 1.0 bar (0 to 15 psig)
0 to 1.4 bar (0 to 20 psig)
0 to 2.0 bar (0 to 30 psig)
0 to 300 mbar (0 to 80 inch wc)
0 to 0.7 bar (0 to 10 psi)
0 to 1.4 bar (0 to 20 psi)
0 to 2.0 bar (0 to 30 psi)
Normal Operating Supply
Pressure
C1 Controllers and Transmitters
(3)
With Optional Travel Stop
Bar
Psig
3.3
48
6.6
96
11
160
19
280
29
420
50
720
83
1200
115
1650
230
3300
380
5500
550
8000
700
10,000
for additional information.
Maximum Allowable Supply Pressure To Prevent
(1)
1.4
2.4
20
35
March 2017
(4)
(5)
MATERIAL
316 stainless steel
MAXIMUM ALLOWABLE STATIC
(2)
PRESSURE LIMITS
Brass
Stainless Steel
Construction
Construction
Bar
Psig
Bar
1.4
20
---
2.8
40
---
2.8
40
6.9
1.4
20
---
2.8
40
6.9
2.8
40
6.9
1.4
20
---
1.4
20
---
2.8
40
---
2.8
40
---
2.8
40
---
2.8
40
---
2.8
40
6.9
2.8
40
---
2.8
40
6.9
1.4
20
---
2.8
40
---
2.8
40
---
---
---
6.9
Internal Part Damage
2.8
2.8
40
40
Psig
---
---
100
---
100
100
---
---
---
---
---
---
100
---
100
---
---
---
100
5