Emerson Fisher C1 Instruction Manual page 45

Pneumatic controllers and transmitters
Table of Contents

Advertisement

Instruction Manual
D103292X012
Figure 23. Typical Reverse Acting Fisher C1 Proportional-Plus-Reset Assembly (continued)
(Refer to figure 26 for the Front View of the Case & Cover Assembly)
NOTES:
ARROW DOWN—RELIEVES ON DECREASING OUTPUT (OUTPUT @ SUPPLY DURING SHUTDOWN)
1
ARROW UP—RELIEVES ON INCREASING OUTPUT (OUTPUT @ ZERO DURING SHUTDOWN)
2
KEYS 80, 81, AND 82 ARE NOT SHOWN
GE31718-A
E1072
Key
Description
 58
Knob, PPS (polyphenylene sulfide)
 59
Knob Spring, steel/zinc pl
 60
Washer, G10100 carbon steel, zinc pl
 61
Machine Screw, steel pl
(1)
 62
Washer
, brass/zinc pl (2 req'd)
 63
Gain Adj Bar, A03600
 64
Washer, 18-8 SST
 65
Spring Adjustor, 18-8 SST
 66
Travel Stop Assembly, SST
 Use w/optional Bourdon tube travel stop
 67* Inner Flexure, S30200
 68* Outer Flexure, S30200
 69
Indicator Scale, aluminum
 70
Bias Spring, SST
*Recommended spare parts
1. This part is included in the Controller Repair Kit.
3. If ordering the bellows (key 71) to change the range of a gauge pressure controller,
also order the appropriate bellows spring (key 80). Also order keys 101, 102, and 103
if you do not have them.
SPRING-OUT CLEANING WIRE
RELAY ASSEMBLY
PROPORTIONAL-PLUS-RESET CONTROLLER WITH
DIFFERENTIAL RELIEF VALVE ASSEMBLY FOR ANTI-RESET WINDUP
C1 Controllers and Transmitters
Key
Description
 71* Gauge Pressure Bellows (input)
 Brass
  0-150 mbar (0-60 inches wc) positive, 0-150 mbar
   (6-60 inches wc) vacuum, and 75-0-75 mbar
    (30-0-30 inches wc) compound
  0-250 mbar (0-100 inches wc) positive
  0-0.35 mbar (0-5 psig) positive and for
   0-350 mbar (0-10 inches Hg) vacuum
  0-0.5 bar (0-7.5 psig) positive
  0-0.7 bar (0-10 psig) positive
  0-1.0 bar (0-15 psig) positive, 0-1.0 bar
   (0-30 inches Hg) vacuum, and 500-0-500 mbar
    (15-0-7.5 psig) compound
  0-1.4 bar (0-20 psig) positive
  0-2.0 bar (0-30 psig) positive and 1.0-0-1.0 bar
   (30-0-15 psig) compound
 Stainless steel,
  0-1.0 bar (0-15 psig) positive, 0-1.0 bar
   (0-30 inches Hg) vacuum, and 500-0-500 mbar
    (15-0-7.5 psig) compound
  0-2.0 bar (0-30 psig) positive, 1.0-0-1.0 bar
   (30-0-15 psig) compound
March 2017
2
1
(3)
45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents