• Equipment must be installed according to applicable local wiring codes and standards.
CONTENTS
Section 2.6.1, "Connecting High AC/DC Power"
Section 2.6.2, "Connecting Low DC Power"
Section 2.6.1

Connecting High AC/DC Power

To connect a high AC/DC power supply to the device, do the following:
DANGER!
Electrocution hazard – risk of death, serious personal injury and/or damage to the device. Make sure
the supplied cover is always installed over high voltage screw-type terminal blocks.
CAUTION!
Electrical hazard – risk of damage to equipment. Do not connect AC power cables to a 12, 24 or 48 VDC
power supply terminal block. Damage to the power supply may occur.
NOTE
The screw-type terminal block is installed using Phillips screws and compression plates, allowing either
bare wire connections or crimped terminal lugs. Use #6 size ring lugs for secure, reliable connections.
1.
Connect the power supply terminal block to the device.
Figure 5: AC Terminal Block Wiring – Pluggable Terminal Block for HIP Power Supplies
1. 3-Position Terminal Block    2. Positive/Live (+/L) Terminal    3. Ground Terminal    4. Negative/Neutral (-/N) Terminal